 Black  Temperature Signal 
  White  Relative Humidity Signal 
  Blue  Signal & Power Reference 
  Brown  Power 
 Clear  Shield 
FIGURE 7-1. HMP60 wiring 
TABLE 7-1. Datalogger Connections 
Wire Label 
Color 
CR800, CR3000, 
CR200(X), CR23X, 
CR1000 
CR10(X), CR510 
21X, CR7 
Temp Signal  Black  Single-Ended Input  Single-Ended Input  Single-Ended Input 
RH Signal  White  Single-Ended Input  Single-Ended Input  Single-Ended Input 
Power & Signal 
Ground 
Blue G  G 
Power 12V  Brown  12 V  12 V  12 V 
Shield Clear 
G 
7.3 Wiring 
Connections to Campbell Scientific dataloggers are given in Table 7-1. The 
probe is measured by two single-ended analog input channels, one for 
temperature and one for relative humidity. 
Always connect the blue lead to the datalogger first, 
followed by the black, white, and clear leads. Connect the 
brown (power) lead last. 
CAUTION 
7.4 Programming 
This section is for users who write their own datalogger programs. A 
datalogger program to measure this sensor can be created using Campbell 
Scientific’s Short Cut Program Builder Software. You do not need to read this 
section to use Short Cut. 