User Manual
HMP60 Temperature and Relative Humidity Probe 
reference and power ground are connected to ground at the datalogger. The 
signal reference/power ground lead serves as the return path for 12 V. There 
will be a voltage drop along this lead because the wire itself has resistance. The 
HMP60 draws approximately 2 mA when it is powered. The wire used in the 
HMP60 (P/N 18159) has resistance of 26.2 Ω/1000 feet. Using Ohm’s law, the 
voltage drop (V
d
), along the signal reference/power ground lead, is given by 
Eq. (1). 
ft  1000  mV 2.45
ft  1000   6.22 mA  2
=
Ω∗=
∗= RI
V
d
 (1) 
This voltage drop will raise the apparent temperature and relative humidity 
because the difference between the signal and signal reference, at the 
datalogger, has increased by V
d
. 
7.6 Absolute Humidity 
The HMP60 measures the relative humidity. Relative humidity is defined by 
the equation below: 
RH
e
e
 100
s
=∗
 (2) 
where RH is the relative humidity, e is the vapor pressure in kPa , and e
s
 is the 
saturation vapor pressure in kPa. The vapor pressure, e, is an absolute measure 
of the amount of water vapor in the air and is related to the dew point 
temperature. The saturation vapor pressure is the maximum amount of water 
vapor that air can hold at a given air temperature. The relationship between 
dew point and vapor pressure, and air temperature and saturation vapor 
pressure are given by Goff and Gratch (1946), Lowe (1977), and Weiss 
(1977). 
When the air temperature increases, so does the saturation vapor pressure. 
Conversely, a decrease in air temperature causes a corresponding decrease in 
saturation vapor pressure. It follows then from Eq. (2) that a change in air 
temperature will change the relative humidity, without causing a change in 
absolute humidity. 
For example, for an air temperature of 20°C and a vapor pressure of 1.17 kPa, 
the saturation vapor pressure is 2.34 kPa and the relative humidity is 50%. If 
the air temperature is increased by 5°C and no moisture is added or removed 
from the air, the saturation vapor pressure increases to 3.17 kPa and the 
relative humidity decreases to 36.9%. After the increase in air temperature, 
there is more energy available to vaporize the water. However, the actual 
amount of water vapor in the air has not changed. Thus, the amount of water 
vapor in the air, relative to saturation, has decreased. 
Because of the inverse relationship between relative humidity and air 
temperature, finding the mean relative humidity is meaningless. A more useful 
quantity is the mean vapor pressure. The mean vapor pressure can be 
computed on-line by the datalogger. CRBasic dataloggers use the 
14 










