Specifications
AM25T Solid State Multiplexer 
10 
04: BR Transform Rf[X/(1-X)] (P59)  ;Calculate RTD resistance R/R0 
 1: 1   Reps 
  2:  1    Loc [ RefTemp_C ] 
 3: 10.025   Multiplier (Rf) 
05: Temperature RTD (P16)  ;Calculate reference temperature 
 1: 1   Reps 
  2:  1    R/R0 Loc [ RefTemp_C ] 
  3:  1    Loc [ RefTemp_C ] 
 4: 1.0   Mult 
 5: 0.0   Offset 
06: Beginning of Loop (P87)  ;Loop through thermocouple channels 
 1: 0   Delay 
 2: 25   Loop Count 
07: Do (P86)      ;Clock the AM25T twice 
 1: 71   Pulse Port 1 
08: Do (P86) 
 1: 71   Pulse Port 1 
09: Thermocouple Temp (DIFF) (P14)  ;Measure the connected thermocouple 
 1: 1   Reps 
  2:  21    2.5 mV 60 Hz Rejection Range 
 3: 1   DIFF Channel 
 4: 1   Type T (Copper-Constantan) 
  5:  1    Ref Temp (Deg. C) Loc [ RefTemp_C ] 
  6:  2--    Loc [ TC_1 ] 
 7: 1.0   Mult 
 8: 0.0   Offset 
10: End (P95)      ;End loop 
11: Do (P86)      ;Turn off AM25T 
  1:  52    Set Port 2 Low 
Example 2. CR10(X) Program for Measuring 25 Type T Thermocouples with the Differential 
Thermocouple Instruction and Long Lead Length Compensation on the RTD Measurement 
*Table 1 Program 
 01: 10   Execution Interval (seconds) 
01: Set Port(s) (P20)  ;Configure Control Ports for 1 millisecond pulse 
 1: 9999   C8..C5 = nc/nc/nc/nc 
 2: 9933   C4..C1 = nc/nc/1ms/1ms 
02: Do (P86) 
  1:  42    Set Port 2 High  ;Turn On AM25T 