Specifications
AM25T Solid State Multiplexer 
12 
12: Beginning of Loop (P87)  ;Loop through thermocouple channels 
 1: 0   Delay 
 2: 25   Loop Count 
13: Do (P86)      ;Clock the AM25T twice 
 1: 71   Pulse Port 1 
14: Do (P86) 
 1: 71   Pulse Port 1 
15: Thermocouple Temp (DIFF) (P14)  ;Measure the connected thermocouple 
 1: 1   Reps 
  2:  21    2.5 mV 60 Hz Rejection Range 
 3: 1   DIFF Channel 
 4: 1   Type T (Copper-Constantan) 
  5:  1    Ref Temp (Deg. C) Loc [ RefTemp_C ] 
  6:  2--    Loc [ TC_1 ] 
 7: 1.0   Mult 
 8: 0.0   Offset 
16: End (P95)      ;End loop 
17: Do (P86)      ;Turn off AM25T 
  1:  52    Set Port 2 Low 
6.2 Example 21X Programs 
The two example 21X programs in this section cover measuring thermocouples 
with the differential measurement instruction. 
Input locations within the measurement loops must be indexed (--), see 
Instruction 87 in the datalogger manual. To index a location, using Edlog ver 
6.0 or greater, move the cursor to the Input location label and press “F4”. To 
index a location with the datalogger keyboard, press the “C” key when 
entering the location number and before the “A” key is pressed. 
TABLE 6-3. Wiring for 21X Examples 
Function AM25T 21X 
+12V Power  12 V  12 V 
Power and Shield Ground 
Clock CLK C1 
Reset RES C2 
RTD Excitation  EX  E1 
Analog Ground  AG 
Common High  HI  1H 
Common Low  LO  1L 