18: Thermocouple Temp (DIFF) (P14)  ;Measure the connected thermocouple 
 1: 1   Reps 
  2:  1    5 mV Slow Range 
 3: 1   DIFF Channel 
 4: 1   Type T (Copper-Constantan) 
  5:  1    Ref Temp (Deg. C) Loc [ RefTemp_C ] 
  6:  2--    Loc [ TC_1 ] 
 7: 1.0   Mult 
 8: 0.0   Offset 
19: End (P95)      ;End loop 
20: Do (P86)      ;Turn off AM25T 
  1:  52    Set Port 2 Low 
6.3 Example CR23X Program 
The CR23X has a special instruction for measuring thermocouples or voltages 
with the AM25T. Example 5 uses the instruction to measure 25 type T 
thermocouples. Instruction 134 automatically compensates for long lead 
lengths. 
TABLE 6-4. Wiring for CR23X Example 
Function AM25T CR23X 
+12V Power  12 V  12 V 
Power and Shield Ground 
G 
Clock CLK C1 
Reset RES C2 
RTD Excitation  EX  E1 
Analog Ground  AG 
Common High  HI  1H 
Common Low  LO  1L 