Specifications
Appendix A. Single-Ended Measurements 
A-6 
instruction has one repetition. If the instruction has two repetitions, then every 
other Input Location will be over written. This effect is illustrated in Table A-
2. The program fragment in Example A-4 generated this effect. 
The multiplexer control instructions are not included in the 
example program fragment. 
TABLE A-2. Values in Input Storage; with Input Location Index and 
without Step Loop Index Instruction 
Pass 18 19 20 21 22 23 
First TC_1 TC_2 
Second  TC_3  TC_4 
Third  TC_5 TC_6 
By adding Instruction 90 (Step Loop Index) with a value of two, the 
measurements will be stored sequential in Input Storage. See Table A-3 and 
the program fragment in Example A-5. 
The multiplexer control instructions are not included in the 
example program fragment. 
TABLE A-3. Values in Input Storage; with Input Location Index and 
Step Loop Index Instruction 
Pass 18 19 20 21 22 23 
First TC_1 TC_2 
Second  TC_3 TC_4 
Third  TC_5 TC_6 
Example A-3. Single Ended Thermocouples, Input Location Not Indexed 
01: Beginning of Loop (P87) 
 1: 0   Delay 
 2: 6   Loop Count 
02: Thermocouple Temp (SE) (P13) 
 1: 2   Reps 
  2:  21    2.5 mV 60 Hz Rejection Range 
 3: 1   SE Channel 
 4: 1   Type T (Copper-Constantan) 
  5:  1    Ref Temp (Deg. C) Loc [ RefTemp ] 
  6:  18    Loc [ TC_1 ] 
 7: 1.0   Mult 
 8: 0.0   Offset 
03: End (P95) 