User guide

PS100, CH100 & BP-ALK Power Supplies
6
Table 3 Typical Battery Capacity for Lead-acid Batteries
as a Function of Temperature
Temperature
(°C)
% of 20°C
capacity
Capacity (Ah)
NP7-12 NP12-12 NP17-12 NP24-12
40 110 7.7 13.2 18.7 26.4
20 100 7 12 17 24
0 84 5.9 10.0 14.2 20.2
-20 72 5.0 8.6 12.2 17.3
N.B. these figures only apply to low discharge rates.
It is recommended that the batteries should not be deeply
discharged below -20°C as there is a risk of ice formation
within the battery which can cause permanent damage.
3.2 AC Adapters (Transformers)
Two different 230V adapters are available from Campbell Scientific Limited in
Europe for use with the lead-acid power supply units. They have different
characteristics in use as explained below. Adaptors with different AC supply
voltages are available to special order.
3.2.1 AC-ADAPT
The AC-ADAPT is only suited for desktop use in low current applications. It can
provide up to 1.2A. If the transformer unit overheats, which is only likely to occur
if the output is short circuited, a safety mechanism will shut it down. In this
unlikely event, reset the safety mechanism manually by removing AC power,
tracing and eliminating the cause of the short circuit, and allowing the transformer
to cool before re-connecting to the mains supply.
The AC-ADAPT is provided with a fixed length of cable on the output side. Many
installations will require this cable to be extended using a suitable length of
compatible cable and an in-line connector. This extension cable is not supplied by
Campbell Scientific unless specifically ordered.
3.2.2 AC-ADAPT2
The AC-ADAPT2 transformer is suitable for permanent installations which
require a wall mounted unit. It is capable of providing more current than the
charger unit needs and so is able to recharge batteries at the maximum rate, and
still provide high current levels to equipment via the power supply. If the
transformer unit overheats, which is only likely to occur if the output is short
circuited, a safety mechanism will shut it down. In this unlikely event, reset the
safety mechanism manually by removing AC power, tracing and eliminating the
cause of the short circuit, and allowing the transformer to cool before re-
connecting to the mains supply.
The AC-ADAPT2 is not provided with output cable unless specifically ordered.
The adapter is fitted with two screw-down terminals for you to connect a suitable
length of cable as required for your application. To fit the cable to the
CAUTION