INSTALLATION OPERATION AND SERVICE MANUAL GAS FIRED WALL HUNG & FLOOR MOUNT RESIDENTIAL COMMERCIAL STAINLESS STEEL BOILERS DynaMax HS SERIES HYDRONIC HEATING Models; DMH081, 101, 151, 201, 251, 211, 261, 291, 391, 501, 601, 701, 801 HOT WATER SUPPLY Models; DMW082 ,102, 152, 202, 252, 212, 262, 292, 392, 502, 602, 702, 802 COMBINATION HEATING/HOT WATER SUPPLY Models; DMC083, 103, 153, 203, 253, 213, 263, 293, 393, 503, 603, 703, 803 H HLW WARNING: If the information in these instructions is not followed
Contents PART 1 1.1 1.2 1.3 1.4 1.5 1.5.1 1.5.2 1.6 1.7 1.8 1.9 1.10 1.11 PART 2 2.1 2.2 2.2.1 2.3 2.3.1 2.4 2.5 2.5.1 2.5.2 2.5.3 2.6 PART 3 3.1 3.2 3.3 3.4 3.5 3.6 3.7 PART 4 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.7.1 4.8 4.9 4.10 GENERAL INFORMATION ............................................................................................................... 1 INTRODUCTION ..............................................................................................................................
.11 4.12 PART 5 5.1 5.2 5.3 5.3.1 5.3.2 5.4 5.4.1 5.4.2 PART 6 6.1 6.2 PART 7 7.1 7.2 7.3 7.4 7.5 PART 8 8.1 8.2 PART 9 9.1 9.2 9.3 9.4 9.5 9.6 9.7 9.7.1 9.8 9.9 9.10 9.11 9.12 9.13 PART 10 10.1 10.2 10.3 10.4 10.5 10.6 10.7 10.8 RELIEF VALVE................................................................................................................................ 18 DHW TUNING VALVE (combination models only) .......................................................................
10.9 10.10 10.11 10.12 10.13 10.14 PART 13 PART 14 PART 15 15.1 15.2 15.2 15.2.1 15.2.2 DOMESTIC HOT WATER WITH PLATE HEAT EXCHANGER ............................................................ 56 TEMPERATURE RISE AT FULL FIRING RATE .................................................................................. 57 LEAD LAG SETUP .......................................................................................................................... 58 LOCAL/REMOTE SWITCH...............................
PART 1 1.1 GENERAL INFORMATION 1) 2) INTRODUCTION The DynaMax HS boiler is a fan assisted boiler based on a push through design which offers several venting options. Heat output is controlled by a one to one air/gas ratio control gas valve which provides seamless modulation. The boiler provides central heating, domestic hot water or combination heating with DHW priority at working pressure up to 160 PSI. It is designed for use with a fully pumped and pressurized water system.
1.5.2 1) 2) 3) 4) End of Sequence Setpoint temperature is satisfied. Power to the gas valve is turned off. Combustion air fan ramps to a stop over the factory preprogrammed time period. Thermostat is now in standby mode waiting for the next “Call for Heat”. WARNING To minimize the possibility of serious personal injury, fire or damage to your appliance, never violate the following safety rules. DO NOT Do not use this appliance if any part of it has been under water.
1.8 REMOVAL OF EXISTING APPLIANCE When an existing appliance is removed from a common venting system, the common venting system is likely to be too large for proper venting of the appliances remaining connected to it. At the time of removal of an existing appliance, the following steps must be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
• • • • • • The appliance must be installed so that the ignition system components are protected from water (dripping, spraying, etc.) during appliance operation and service (circulator replacement, control replacement, etc.) Appliances located in a residential garage and in adjacent spaces that open to the garage and are not part of the living space of a dwelling unit must be installed so that all burners and burner ignition devices have a minimum clearance of not less than 18" (46cm) above the floor.
Table 2: DynaMax HS Wall Hung Service Clearances Service Clearance, Inches (cm) Model Front Top Right Side Left Side Rear 80 24” (61cm) 3” (8 cm) 4” (10 cm) 4” (10 cm) 0” (0 cm) 100 24” (61cm) 3” (8 cm) 4” (10 cm) 4” (10 cm) 0” (0 cm) 150 24” (61cm) 3” (8 cm) 4” (10 cm) 4” (10 cm) 0” (0 cm) 200 24” (61cm) 3” (8 cm) 4” (10 cm) 4” (10 cm) 0” (0 cm) 250 24” (61cm) 3” (8 cm) 4” (10 cm) 4” (10 cm) 0” (0 cm) Figure 3: DynaMax HS Wall Hung Model Dimensions Table 3: Appliance D
Table 4: DynaMax HS Floor Mount Service Clearances Service Clearance, Inches (cm) Model Front Top Right Side Left Side Rear 210 12” (31cm) 24” (61cm) 0” (0cm) 12” (31cm) 14” (36 cm) 260 12” (31cm) 24” (61cm) 0” (0cm) 12” (31cm) 14” (36 cm) 299 12” (31cm) 24” (61cm) 0” (0cm) 12” (31 cm) 14” (36cm) 399 12” (31cm) 24” (61cm) 0” (0cm) 12” (31 cm) 14” (36 cm) 500 12” (31cm) 24” (61cm) 0” (0cm) 12” (31 cm) 14” (36 cm) 600 12” (31cm) 24” (61cm) 0” (0cm) 12” (31 cm) 14” (36
Figure 5: DynaMax HS Wall Hung Service Clearances Figure 6: DynaMax HS Floor Mount Service Clearances 7
PART 2 It is extremely important to follow these venting instructions carefully. Failure to do so can cause severe personal injury, death or substantial property damage. 2.1 GENERAL VENTING GUIDE The DynaMax HS Wall Hung is a category IV condensing appliance, 97% efficient unit. The DynaMax HS Floor Mount is a category II condensing appliance, 97% efficient.
Table 6: Maximum Flue Temperature for Various Vent Materials Vent Material Maximum Flue Temperature [oF] PVC 149 CPVC 194 PPE AL29-4C 230 1) 300+, limited only by rating of seals 300+, limited only by rating of seals 316L Stainless Steel o Stack temperature is typically between 15-30 F above inlet water temperature depending on model size and firing rate.
Air inlet point for multiple boiler air inlets must be provided with an exterior opening which has a free area equal to or greater than the total area of all air inlet pipes connected to the common air inlet. This exterior opening for combustion air must connect directly to the outdoors. The total length of the combined air inlet pipe must not exceed a maximum of 100 equivalent feet (30.5m).
Location of a Sidewall Air Inlet Cap 1) Total length of piping for air inlet must not exceed the limits stated in Table 7. 2) Point of termination for the sidewall air inlet cap must be located a minimum of 12 inches (0.30m) away from the flue gas termination, but never above. 3) Air piping must terminate in a down-turned elbow to avoid recirculation of flue products into the inlet air stream. 4) DO NOT terminate closer than 4 feet (1.
Location of a Vertical Air Inlet Opening 1) The total length of piping for inlet air must not exceed the limits given in Table 7. o 2) The air inlet consists of two 90 elbows installed at the point of termination for the vertical air inlet pipe. o o A 90 elbow and a 90 street elbow may be used to make this assembly. If a straight piece of pipe is used between the two elbows, it should not exceed 6” (0.15m) in length. The air inlet opening must be at least 1 foot below the vent opening.
PART 3 GAS CONNECTION Verify that the appliance is supplied with the type of gas specified on the rating plate. Consult factory for installations at high altitude. 3.1 • • • • • • The appliance and its individual gas shut-off valve must be disconnected from the supply piping when pressure testing the gas supply piping at pressures above ½ PSI Table 9: Gas Pressures at Inlet to Appliance GAS CONNECTION Safe operation of unit requires properly sized gas supply piping. See gas line sizing data.
IMPORTANT Upon completion of initial installation or following any repair work on the gas system, leak test all gas connections with a soap solution while the main burner is firing. Immediately repair any leak found in the gas train or related components. DO NOT operate an appliance with a leak in the gas train, valves or related gas piping. 3.
This appliance uses a single cylindrical burner installed horizontally into the cavity located in the center of the heat exchanger. A unique burner is used for each one of the DynaMax HS models. Burners may NOT be interchanged between different Btu/hr input models. The burner consists of a round mounting flange welded to a ported stainless steel mixing tube. This stainless steel tube is covered with a close fitting, knitted stainless steel metal fiber alloy material that forms the burner outer surface.
Table 10: Minimal System Pipe Size shelter will help to minimize nuisance problems with electrical connections and will allow easier servicing of the appliance under severe weather conditions. 4.
condominiums, apartments and motels and typically used in conjunction with tempering valves to achieve temperature control. Table 11: Flow and Pressure Drop at a Given Temperature Rise (Hydronic Heating) Input, Btu/Hr 30 °F (16.7 °C) 35 °F (19.4 °C) Temp Rise Temp Rise USGPM (min. flow) ∆P Ft. USGPM. (min. flow) ∆P Ft. 5.0 8.2 4.3 6.2 100,000 6.3 12.3 5.4 9.4 150,000 9.5 10.4 8.1 7.8 199,000 12.6 7.2 10.8 5.8 250,000 15.8 11.5 13.5 8.7 299,000 18.9 9.3 16.2 7.
4.8 FLOW PROVING DEVICE (wall mount models and combination models only) Figure 20: Flow Proving Device CAUTION Remove jumper when connecting to 24 VAC circuit. Figure 21: Low Water Cut Off Electrical Connections (Watts) Connection detail for placing L.W.C.O in 24V circuit WARNING: Be sure to remove the jumper between H and P1 Water Flow Switch The flow proving device is designed to detect when flow is present.
PART 5 5.2 ELECTRICAL & CONTROLS IT IS EXTREMELY IMPORTANT THAT THIS UNIT BE PROPERLY GROUNDED! 5.1 ELECTRICAL CONECTIONS Table 14: DynaMax HS Electrical Requirements HIGH LIMIT A manual reset fail-safe high limit aqua-stat control is inside the appliance and the control bulb is installed in a dry well in the heat exchanger outlet. The setting of this control limits o maximum discharge water temperature to 210 F (CPVC, o AL29-4C, Stainless) and 185 F (PVC).
5.3.2 IGNITION MODULE LOCKOUT FUNCTIONS The DynaMax HS Controller may lockout in either a manual reset condition requiring pushing the reset button to recycle the control for a CSD1 requirement or an automatic reset condition. Pushing the “OK” with the control in a hard lockout condition is the only way to reset the DynaMax HS Controller. Turning the main power “OFF” and then “ON” or cycling the thermostat will not reset a hard lockout condition.
PART 6 6.1 CONTROL PANEL DYNAMAX HS CONTROLLER The appliance is provided with an operator interface panel at the front. On a DynaMax HS Wall Hung boiler the DynaMax HS Controller can be accessed by removing the upper stainless steel jacket and the lower black sheetmetal jacket which are each held on by two (2) screws. On a DynaMax HS Floor Mount boiler the DynaMax HS Controller can be accessed by carefully lifting off the black-coloured top cover which is held on by four (4) snap lock fasteners. 6.
PARAMETER DESCRIPTION Boiler name DynaMax HS model State Indicates current boiler operation sequence Indicates origin of call for heat (CH, DHW, Lead Lag) User, Installer Demand Access Status Outdoor Error Pressing provides additional temperature information. Figure 26: Temperature screen o Outdoor Temperature [ F], if equipped Alert or Lockout. Section 5.4 provides additional details. Pressing provides additional troubleshooting information on the diagnostic screen.
Central Heat Programming Instructions Modulation: Boiler Inlet, Boiler Fixed Setpoint Operation (Standalone) Description Electrical Connection(s) • Boiler operates at a fixed setpoint • Modulates on boiler inlet sensor (default) • Heat demand is generated when Remote Operator is closed.
Modulation: Boiler Inlet, Outdoor Reset Operation (Standalone) Description Electrical Connection(s) • Boiler operates with variable setpoint determind by outdoor reset curve • Modulates on inlet sensor (default) • Heat demand is generated when Remote Operator is closed.
Modulation: System Sensor, Outdoor Reset Operation (Standalone) NOTE: Outdoor Reset Module (PN: 50022037-001) and outdoor sensor (PN: C7089U1006) required Description Electrical Connection(s) Programming Instructions 1) Connect Remote Operator • Boiler operates with variable 2) Connect System sensor to System/Outdoor contacts setpoint determind by 3) Connect Outdoor Sensor to J3 ECOM connector outdoor reset curve 4) Place both toggle switches in LOCAL • Modulates on system sensor 5) Press and select Login •
4-20mA/ 0-10Vdc Setpoint Operation (Standalone) Consult Additional Boiler Parameters section in manual on page 33 using parameter address 583 and 584. 4-20mA/ 0-10Vdc Firing Rate Operation (Standalone) Description Electrical Connection(s) • Boiler operates with variable setpoint determined by 420mA incoming signal • Modulates on header sensor • Heat demand is generated when Remote Operator is closed and 4-20mA or 010Vdc signal is present.
Domestic Hot Water Programming Instructions Modulation: Fixed Setpoint Operation (Standalone) Description Electrical Connection(s) • Boiler operates at a fixed DHW setpoint • Modulates on boiler inlet sensor (default) • Heat demand is generated when Remote Operator is closed. DHW Sensor/ Stat, if required.
Instantaneous DHW with Brazed Plate Heat Exchanger (combination models) Description Electrical Connection(s) • Boiler operates at a fixed DHW setpoint • Modulates on boiler inlet sensor (default) • Heat demand is generated when Remote Operator is closed. DHW Sensor/ Stat, if required.
Lead Lag Programming Instructions Master Boiler • Description Master boiler lead lag setup Electrical Connection(s) Programming Instructions 1) Place both toggle switches in LOCAL 2) Press and select Login 3) Select Advanced Setup 4) 5) 6) 7) 8) 9) 10) Select System Select System ID & Access Verify MB1 Modbus address = 1 Verify MB2 Modbus address = 1 Select Lead Lag Config Select Lead Lag Master Config Select Master enable = Enable Fixed Setpoint operation 11) Select Setpoint, and enter desired setpoin
Slave Boiler Description • Slave boiler lead lag setup Electrical Connection(s) Programming Instructions 1) Place both toggle switches in LOCAL 2) Press and select Login 3) Select Advanced Setup 4) 5) 6) 7) 8) 9) Select System Select System ID & Access Select MB1 Modbus address = 2. To be in sequential order Select MB2 Modbus address = 2.
Outdoor Sensor connected to Slave boiler 2 (DRH ONLY) Description Electrical Connection(s) • Slave boiler outdoor sensor configuration • When done correctly, the outdoor temperature will be shown on the Master boiler Programming Instructions Slave Boiler 1) Place both toggle switches in LOCAL 2) Press and select Login 3) Select Advanced Setup 4) Select Sensor Configuration 5) Select Outdoor temp src and Press 6) Select S5 and Press Master Boiler 7) Place both toggle switches in LOCAL 8) Press and select L
Base load rate adjustment Description • Upon a call for heat the lead boiler will fire to the specified base load rate (80%). If the temperature is not within Error threshold (5oF) of setpoint after Interstage delay (2 minutes) a lag boiler will be brought online and will also fire at the base load rate specified. • Modulation of boilers will only occur after all boilers in the Lead Lag system are firing at the specified base load rate (80%).
Additional Boiler Parameter Instructions There are some parameters that are not accessible through the Advanced Setup within the HAPI display. o o Temperature related parameters must be entered in degrees Celcius. For example, 50 F = 10.0 C. The value “100” is entered into the display. Refer to the next page for a conversion table. Safety related parameters should not be altered as this will send the control into a Lockout 2 condition, and the HAPI display cannot recover from this.
Fahrenheit [oF] -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 Celcius [oC] -28.9 -23.3 -17.8 -12.2 -6.7 -1.1 4.4 10.0 15.6 21.1 26.7 32.2 37.8 43.3 48.9 54.4 60.0 65.6 71.1 76.7 82.2 87.8 93.
Boiler Setup Programming Instructions Adjust lightoff rate Description • Adjust ignition speed on lightoff • This may need to be adjusted to achieve smooth lightoffs cannot be achieved through combustion settings • All DynaMax HS boilers leave the factory with an ignition fan speed of 3000 RPM Programming Instructions 1) Place both toggle switches in LOCAL 2) Press and select Login 3) Select Advanced Setup 4) Select Burner Control Ignition 5) Select Adjustable lightoff rate, and enter desired lightoff rat
View burner run time, pump cycles Description • To view burner run time, pump cycles for maintenance and service purposes Programming Instructions 1) Place both toggle switches in LOCAL 2) Press and select Login 3) Select Advanced Setup 4) Select System Config 5) Select Statistics Config 36
PART 7 COMPONENTS 7.1 DIRECT SPARK IGNITER The direct spark igniter is inserted directly through the combustion chamber front door and held in place by two torx-20 screws. Care must be taken when removing and/or installing the igniter. Always remove the igniter prior to removing the fan assembly for inspection of the burner and heat exchanger. Figure 27: Direct Spark Igniter 7.
PART 8 TROUBLESHOOTING Table 18: Troubleshooting Table COMPONENT Incoming Power Transformer Tripped Pump Fails to Circulate FAILURE MODE • Two wires interchanged • The 24Volts and 120 Volts wired are interchanged • Wiring Issue • Faulty Pump on a wet rotor pump • Air in the piping system Relief Valve • Internal Fault on DynaMax HS Controller • System pressure exceeds relief valve setting • Flow Proving Device/ LWCO contacts are open Flow Proving Device/ LWCO • The boiler has failed to ignite the b
SYMPTOM FAILURE MODE • The DynaMax HS boiler was running and flame signal suddenly disappeared.
SYMPTOM Temperature Overshoot Sensor Not Connected Fan Not Turning Blocked Flue Switch Flame Detection is out of Sync FAILURE MODE • Stack temperature has exceeded the limit set on the boiler.
Manual Reset Codes* # 0 1-31 47 49 64 67 79 82 91 92 93 95 96 105 106 107 108 109 112 113 149 Description None Internal hardware error Flame rod to ground leakage 24VAC low/high Fan speed not proved, ignition failure Blocked flue condition Heater Outlet high limit tripped o o Stack limit tripped (PVC: 149 F, CPVC: 194 F, o o PPE: 230 F, SS, AL29-4C: 250 F) Inlet sensor fault Outlet sensor fault DHW sensor fault Stack sensor fault Outdoor sensor fault Flame detected out of sequence Flame lost in Main Flame
Ignition Failed displayed on screen Hold 109: Ignition failed An ignition error occurs when 3 consecutive attempts at lighting the burner have failed. This is a manual reset error where the technician must press OK to clear the error.
Hold 67: ILK OFF (Flow Switch, LWCO, Gas Pressure Switch, Blocked Flue Switch) Alert 303: Abnormal Recycle: ILK off during drive to Purge Alert 304: Abnormal Recycle: ILK off during Measured purge time Alert 305: Abnormal Recycle: ILK off during Drive to Pre-igntion Alert 306, 307: Abnormal Recycle: ILK off during Pre-ignition Alert 308: Abnormal Recycle: ILK off during Main Flame Alert 309: Abnormal Recycle: ILK off during Ignition Period This error can indicate a blocked flue or blocked intake condition,
Hold 67: ILK OFF (Flow Switch, LWCO, Gas Pressure Switch, Blocked Flue Switch) Alert 303: Abnormal Recycle: ILK off during drive to Purge Alert 304: Abnormal Recycle: ILK off during Measured purge time Alert 305: Abnormal Recycle: ILK off during Drive to Pre-igntion Alert 306, 307: Abnormal Recycle: ILK off during Pre-ignition Alert 308: Abnormal Recycle: ILK off during Main Flame Alert 309: Abnormal Recycle: ILK off during Ignition Period The flow switch is not closed or the low water cutoff (LWCO, optiona
Stack limit exceeded displayed on screen Alert 125: Modulation was limited due to stack limit Alert 353: Abnormal recycle: stack limit A flue gas error occurs when the stack temperature has exceeded the maximum limit allowed by the vent material. This is an o automatic reset error, when the stack temperature drops 20 F below the limit allowed the boiler is allowed to restart and an ignition o attempt is made if the call for heat is not yet satisfied.
Alert 291: Abnormal Recycle: Flame was not on at end of ignition Alert 294: Abnormal Recycle: Flame was lost during Run Alert 324: Abnormal Recycle: Hardware flame bias Alert 377: Abnormal Recycle: Hardware flame bias delta This type of failure indicates a flame rectification signal issue through the flame rod.
To adjust the high-fire setting 8.1 SETTING THE CORRECT COMBUSTION 1) Press the Switch the main power off to the boiler by placing the toggle switch in the ‘OFF’ position 2) Select Test and press 2) Switch the main power on to the boiler and adjust set point so that boiler begins ignition sequence. 3) Select Forced Rate and press 3) Observe the boiler as it goes through its startup cycle and operates at high fire.
DM 500 – 800 DM 299 – 399 Figure 58: DM 500 - 800 Gas Valve Figure 57: DM 299 – 399 Gas Valve Low-fire air gas ratio adjustment (use Torx 40 for adjustment, clockwise increases CO2) Lift top cover to access high fire air/gas ratio adjustment (use 3mm allen key for adjustment, counterclockwise increases CO2) High-fire air gas ratio adjustment (Use slotted screwdriver for adjustment, counter-clockwise increases CO2) Low-fire air/gas ratio adjustment, use slotted screwdriver for adjustment, clockwise inc
PART 9 MAINTENANCE 9.3 CLEANING BOILER HEAT EXCHANGER Figure 32: Heat Exchanger & Burner Assembly CAUTION It is important that all gas appliances be serviced by a qualified technician trained by Camus Hydronics. It is in your own interest and that of safety to ensure that all local codes, and all the “NOTES” and “WARNINGS” in this manual are complied with.
12) Brush the heat exchanger with a nylon bristle brush. DO NOT use a metal brush. Re-vacuum the heat exchanger. Many jurisdictions will require the acidic condensate to be neutralized before it can be placed in a drain system. • 13) Finish cleaning by wiping down the boiler heating surfaces with a clean, damp cloth. 14) Rinse out any additional debris with a low pressure water supply. Start rinsing from the rear of the heat exchanger and slowly working your way towards the front of the heat exchanger.
on an annual basis. An appliance installed in a dust or dirt contaminated environment will require inspection and cleaning on a more frequent schedule. The fan assisted combustion process may force airborne dust and dirt contaminants, contained in the combustion air, into the burner. With sustained operation, non-combustible contaminants may reduce burner port area, reduce burner input or cause non-warrantable damage to the burner. Never operate this appliance during construction.
9.10 GAS VALVE VOLTAGE This appliance uses a transformer to supply a 24 volt signal to the Honeywell SOLA. The voltage on the secondary side should be 24 to 28VAC when measured with a voltmeter. A secondary voltage of 21VAC or less supplied to 24VAC components may cause operational problems. 9.11 • • • • • FREEZE PROTECTION FOR INDOOR & OUTDOOR INSTALLATIONS Installations are not recommended in areas where the danger of freezing exists.
PART 10 INSTALLATIONS WARNING Before starting the boiler, smell near the floor and around the boiler for any gas odours or any unusual odour. Remove the stainless steel jacket and smell the interior of the boiler. If there is any sign of a gas leak, do not proceed with startup. Repair all the leaks before attempting to start the boiler. WARNING Propane boilers ONLY – Your local propane supplier adds an odorant to the propane gas to allow for propane gas leak detection.
10.7 a) Boiler Set-Up SUMMARY 1) Typical Boiler Installations General Plumbing Rules 1) Check all local codes. 2) For serviceability, always install unions. 3) Always pipe pressure relief valve to an open drain. 4) Locate system air vents at highest points of system. 5) Expansion tank must be installed near the boiler and on the suction side of the system pump. 6) Support all water piping. 7) Place drip pan underneath boiler.
3) 4) 5) 6) 10.10 1) 2) 3) 4) 5) For example in some cases it may be the bath tub and in some cases it may be the clothes washer. Allow the DynaMax HS to fire up and reach full fire under maximum hot water load demand conditions. Observe the outlet water temperature and close the tuning valve gradually as outlet temperature starts to drop. Allow the system to reach equilibrium between adjustments to the tuning valve.
10.11 LEAD LAG SETUP The following components are needed for a Lead Lag setup 1) 10kΩ System Sensor Turn off all the boilers before beginning the setup process. To setup the DynaMax HS lead lag system follow the instructions: System Sensor Insert the supplied 10kΩ system sensor into the building loop. The wires coming out of the system sensor should be connected to pin#5 and #6 of the green DynaMax HS terminal board. NOTE The use of a system sensor is required in lead lag operation.
10.12 LOCAL/REMOTE SWITCH The local remote switch mounted on the terminal board is designed to generate a call for heat either relying on an external contact closure (Remote) or enabling the boiler locally (local). When Remote is selected via the SPDT switch the Remote Operator contacts on the terminal board must be closed to initiate a call for heat. When Local is selected via the SPDT switch a constant call for heat is generated which will enable the boiler to proceed to a trial for ignition.
PART 13 PIPING DIAGRAMS Figure 31: Single Boiler Hydronic Heating Zoned Piping Arrangement Pressure Reducing Valve Pressure Gauge Expansion Tank Zone Circulator Ball Valve Flow Check Valve Air Separator DynaMax HS Boiler Note: 1) 2) Temperature / Pressure Gauge Size main header to minimize induced flow through zones Separate boiler loop as shown is recommended for system piping greater than 50 equivalent feet.
Figure 32: Single Combination Boiler Zoned Piping Arrangement Pressure Reducing Valve Pressure Gauge Expansion Tank Zone Circulator Ball Valve Flow Check Valve Air Separator DynaMax HS Boiler Temperature / Pressure Gauge Drain Union Anti-scald Mixing Valve Note: 1) 2) Size main header to minimize induced flow through zones Separate boiler loop as shown is recommended for system piping greater than 50 equivalent feet.
Figure 33: Single Boiler Hydronic Heating & Indirect Storage Tank Zoned Piping Arrangement Pressure Reducing Valve Pressure Gauge Expansion Tank Zone Circulator Air Separator Flow Check Valve Ball Valve Anti-scald Mixing Valve DynaMax HS Boiler Hot Water Out Cold Water In Temperature / Pressure Gauge Drain Union Indirect DHW Tank Note: 1) 2) Size main header to minimize induced flow through zones Separate boiler loop as shown is recommended for system piping greater than 50 equivalent feet.
Figure 34: Single Boiler Hydronic Heating & Direct Storage Tank Zoned Piping Arrangement Cold Water In Hot Water Out Anti-Scald Mixing Valve Cold Water In DHW Sensor Union Direct DHW Tank 63
Figure 35: Multiple Boiler Hydronic Heating Zoned Piping Arrangement Pressure Reducing Valve Pressure Gauge Expansion Tank Zone Circulator Ball Valve Flow Check Valve Air Separator System Sensor DynaMax HS Boiler (Master, M1) Temperature/ Pressure Gauge DynaMax HS Boiler (Slave, S2) Drain Union Note: 1) 2) Size main header to minimize induced flow through zones Location of system sensor is based on single speed building circulator.
PART 14 EXPLODED VIEW & PARTS LIST DYNAMAX HS WALL HUNG 65
DYNAMAX HS FLOOR MOUNT 66
Ref # 1 2 3 Name of Part Heat Exchanger Burner Heat Exchanger Flange (complete with gaskets) 4 Heat Exchanger Flange Nuts 5 Igniter 6 7 8 9 10 Flame Sensor Igniter/Flame Sensor Screws DynaMax HS Controller DynaMax HS Display Condensate Neutralizer Box Part ID ALL 4 + 1 Wall 5 + 2 Wall 8 + 4 Wall 8 + 4 Floor 10 + 6 Floor 15 + 8 Floor 18 + 10 Floor 21 +11 Floor 24 + 12 Floor 221.042.001-A 221.039.001-A 221.041.001-A 221.037.001-A 221.038.001-A 2437.003 2416.
Ref # Name of Part Part ID ALL 59896343 (UPS15-58FRC) Hydronic Heating/ Combination Pump 14 DHW Pump 52722512 (UPS26-99FC) PL30 PL36 E12 182212-667 (E22) E7B E9B E12B E33B 127091.1.
DynaMax HS Models Ref # Name of Part Part ID 80 100 150 200 34 Plastic Bezel Bezel HS X X X X X 35 Bracket for Neutralizer Box 14-5419 X X X X X 36 Air Inlet/ Vent Adapter FSA-HEX03 X X X X X LB31-20X X X X 37 Plate Heat Exchanger (Combination Models ONLY) X X ALL 38 DynaMax HS Floor Front Panel 39 DynaMax HS Floor Base Panel 41 Floor Back Panel LB31-40X LB31-50X LB31-80X 14-5501-20-25 14-5501 14-5502 210 250 260 299 399 X X X X X X X X 500 X X X
DynaMax HS Models 210 250 260 299 Ref # Name of Part Part ID 57 Top Cover Assembly 14-5521 X X 58 Dashboard DASHBOARD HS X 59 Bracket for Neutralizer Box 14-5525 X 60 Rubber Bushing 33-0101 X X X X Condensate Pan Brace 14-5417 X X X X 62 63 Cover Plate 64 Standoff Electrical Strip Plate Protector Air Intake Adapter Plastic Flange with 3” Street Elbow 66 67 68 69 70 72 73 74 75 X 14-5420 X 44-0008 14-5546 76 800 X X X X X X X X X X X X X X X X X
Ref # Name of Part DynaMax HS Models Part ID ALL 83 Flue Sensor 84 Outdoor Sensor 85 DHW Sensor (Clip on) 86 Gas Valve Elbow NTCSENSOR-003 NTCSENSOR-004 NTCSENSOR-001 80 100 150 200 210 250 260 X X X X X X X 88 Relief Valve 89 Wiring Harness Firing Valve X X X 45900441-015B X 91 92 93 Expandable Air Inlet Adapter w/o Pressure Test Point Expandable Air Inlet Adapter X X X X X 10-407-05 10-604-10 77-0035 77-0036 X X X X X X X X 800 X X X X X X X X X
Ref # 103 104 105 106 107 108 109 110 111 DynaMax HS Models 210 250 260 299 Name of Part Part ID 80 100 150 200 X X X X Rubber Air Sleeve 1056-22 1056-33 1056-44 1056-55 GM10-25-074-09 X X X X X X X X X X X X X X X X X X X X X Burner Gasket Fan Gasket/ Mixing Chamber Gasket Air Inlet Gasket Current Transformer (Combination Models only) Target disk Washer for Target disk Counter sunk head screw M4x16 for target disk Vent Gasket ALL X X X X 399 500 700 X X X X X
PART 15 15.
15.
75
15.2 FIELD WIRING All wires being placed into the terminal block should be horizontal for at least an inch to ensure sufficient electrical conductivity. 15.2.1 System Sensor The temperature of the primary return can be controlled by installing a system sensor. The system sensor must be used in all lead lag modes, and must be enabled through the DynaMax HS controller. 15.2.
15.
CONDENSING BOILER LIMITED WARRANTY Camus Hydronics Limited (“Camus”) extends the following LIMITED WARRANTY to the owner of this appliance, provided that the product has been installed and operated in accordance with the Installation Manual provided with the equipment. Camus will furnish a replacement for, or at Camus option repair, any part that within the period specified below, shall fail in normal use and service at its original installation location due to any defect in workmanship, material or design.
CAMUS Hydronics is a manufacturer of replacement parts for most copper finned water heaters and heating boilers as well as a The CAMUS CERTIFIED! Seal assures you that Reliability, Efficiency & serviceability are built into every single unit! For more information supplier of specialty HVAC products. Our service line is open 24 hours, 7 days a week! on our innovative products from CAMUS Hydronics Limited, call 905-696-7800 today. CAMUS HYDRONICS LTD.