Service manual
5
Table 2: DynaMax HS Wall Hung Service Clearances
Model
Service Clearance, Inches (cm)
Front Top Right Side Left Side Rear
80
24” (61cm) 3” (8 cm) 4” (10 cm) 4” (10 cm) 0” (0 cm)
100
24” (61cm) 3” (8 cm) 4” (10 cm) 4” (10 cm) 0” (0 cm)
150
24” (61cm) 3” (8 cm) 4” (10 cm) 4” (10 cm) 0” (0 cm)
200
24” (61cm) 3” (8 cm) 4” (10 cm) 4” (10 cm) 0” (0 cm)
250
24” (61cm) 3” (8 cm) 4” (10 cm) 4” (10 cm) 0” (0 cm)
Figure 3: DynaMax HS Wall Hung Model Dimensions
Table 3: Appliance Dimensions and Specifications
Model
Depth Dim.
"A" [in.]
Dim.
"B"
[in.]
Equivalent
Length of Vent & Air
Intake Pipes at Recommended
Diameter, [in.]
Water
Connection
at Boiler
[in.] NPT
Gas Connection
at Boiler [in.] NPT
Over 25'
and up to
100'
Over 15'
and up to
25'
Up to 15'
80
16 1/2 12 3 3 2 1 1/2
100
16 1/2 12 3 3 2 1 1/2
150
16 1/2 12 3 3 2 1 1/2
200
23 1/2 19 3 3 2 1 1/2
250
23 1/2 19 3 3 2 1 1/4 1/2
Maintain minimum specified clearances for adequate operation. All installations must allow sufficient space for servicing the vent
connections, water pipe connections, circulating pump, bypass piping and other auxiliary equipment, as well as the appliance