Service manual
23
Central Heat Programming Instructions
Modulation: Boiler Inlet, Boiler Fixed Setpoint Operation (Standalone)
Description
Electrical
Connection(s)
Programming Instructions
•
Boiler operates at a fixed
setpoint
• Modulates on boiler inlet
sensor (default)
• Heat demand is generated
when Remote Operator is
closed.
1)
Place both toggle switches to
LOCAL
2) Press
and select Login,
3)
Select Quick Start
4) Select CH Setpoint, and enter desired setpoint using 5-way control
The setpoint can be chaged on screenby using the or buttons and
press
5) Place Local/Remote switch to REMOTE for remote enable operation (if
required)