Instantaneous DHW with Brazed Plate Heat Exchanger (combination models)
Description
Electrical Connection(s)
Programming Instructions
Boiler operates at a fixed
DHW setpoint
Modulates on boiler inlet
sensor (default)
Heat demand is generated
when Remote Operator is
closed.
DHW Sensor/ Stat, if required.
1)
Place both toggle switches in
LOCAL
2) Press
and select Login
3)
Select Advanced Setup
4) Select DHW Config
5) Select Demand switch = Plate Heat Exch, and Press
6) Select Mod sensor = DHW
7) Select DHW Setpoint, , and enter desired setpoint using 5-way control
8) Place right hand toggle switch setting to REMOTE for remote operation (if
required)