Lead Lag Programming Instructions
Master Boiler
Description
Electrical Connection(s)
Programming Instructions
Master boiler lead lag setup
1)
Place both toggle switches in
LOCAL
2) Press
and select Login
3)
Select Advanced Setup
4) Select System
5) Select System ID & Access
6) Verify MB1 Modbus address = 1
7) Verify MB2 Modbus address = 1
8) Select Lead Lag Config
9) Select Lead Lag Master Config
10) Select Master enable = Enable
Fixed Setpoint operation
11) Select Setpoint, and enter desired setpoint using 5-way control
4-20mA/ 0-10Vdc setpoint operation
11) Select Setpoint Source = 4-20mA, and Press
12) Consult Additional Boiler Parameters section in manual on page 33 using
parameter address 560 and 561.
13) Select Lead Lag Slave Config
14) Select Slave enable = Enabled via SOLA master, and Press