Service manual

30
Slave Boiler
Description
Electrical Connection(s)
Programming Instructions
Slave boiler lead lag setup
1)
Place both toggle switches in
LOCAL
2) Press
and select Login
3)
Select Advanced Setup
4) Select System
5) Select System ID & Access
6) Select MB1 Modbus address = 2. To be in sequential order
7) Select MB2 Modbus address = 2. To be in sequential order
8) Select Lead Lag Config
9) Select Lead Lag Slave Config
10) Select Slave enable = Enabled via SOLA master, and Press