Boiler Setup Programming Instructions
Adjust lightoff rate
Description
Programming Instructions
Adjust ignition speed on
lightoff
This may need to be adjusted
to achieve smooth lightoffs
cannot be achieved through
combustion settings
All DynaMax HS boilers leave
the factory with an ignition
fan speed of 3000 RPM
1)
Place both toggle switches in
LOCAL
2) Press
and select Login
3)
Select Advanced Setup
4) Select Burner Control Ignition
5) Select Adjustable lightoff rate, and enter desired lightoff rate using 5-way control and press
Adjust stack limit
Description
Programming Instructions
Adjust stack limit based on
vent material used
PVC: 149
o
F
CPVC: 194
0
F
PP, AL29-4C, Stainless steel:
230
o
F
1)
Place both toggle switches in
LOCAL
2) Press
and select Login
3)
Select Quick Start
4) Select Stack Limit