Service manual

42
SYMPTOM FAILURE MODE ANALYSIS
Temperature
Overshoot
• Stack temperature has exceeded
the limit set on the boiler.
• Alert 125, 353
• PVC: Reduce desired setpoint to less than 140
o
F.
• Measure the resistance of the flue sensor at room
temperature, it should be approximately 10k.
• PVC: 149
o
F
• CPVC: 194
o
F
• PPE: 230
o
F
• Stainless Steel, AL29-4C: 250
o
F
• Outlet temperature has exceeded
limit temperature
• Alert 63, 67, 79, 137, 276-281
• ILK OFF
Verify that the system is full of water and that all air has
been properly purged from the system
• Verify that the boiler is piped properly.
• Verify that adequate power is supplied to pump on a call
for heat. If voltage cannot be detected check wiring
• Verify pump is circulating when power is supplied. If so,
pump impeller may be stuck.
• If power is present during a call for heat, but the pump still
does not circulate, replace the pump.
• Replace the Dyna
Max
Controller, if necessary.
Sensor Not
Connected
• Inlet sensor, Alert: 91
• Outlet sensor, Alert: 92
• DHW sensor, Alert: 93
• Flue sensor, Alert: 95
• Outdoor sensor, Alert: 96
• Verify that the sensors are connected
• Verify that they are wired correctly.
• Measure the resistance of the sensors, 10k sensors.
• Replace the sensor if necessary
Fan Not Turning
• Fan refuses to rotate
• Alert 122, 123, 128, 129, 130,131,
132
• Check fan power wires
• Fan signal wires are interchanged
• Minimum fan speed must be greater than 1500 RPM
Blocked Flue Switch
• Check gas pressure switches, if
equipped
• Alert 63, 67, 79, 137, 276-281
I
LK
OFF
• Blocked flue switch wire(s) is/are loose
• Blocked flue switch is set too light if it trips at full fan
speed, reduce sensitivity by turning screw 1 turn
clockwise.
Flame Detection is
out of Sync
• Flame detection is present when no
visible signs of a flame exist
• Lockout 105, 158
• Verify supply voltage for proper polarity.
• Check external wiring for voltage feedback
• Check internal wiring for proper connections
• Check the flame sensor and verify that it is clean
• Replace DynaMax HS Controller
Blank Display
Screen
• Blank display screen • Check S4 switch position on ignition module. Switch is
pushed towards J5 connector
• Check that display is connected to the standalone
connector on the back of the display
Replace fuse with factory 3.15A fuse.
DO NOT use alternates as it may damage the DynaMax
HS
Controller
Internal Fault
• Alert 3-9, 20-31
• Lockout 10-18, 32-46, 58-60 ,97-
99, 143
-
148
• Reset SOLA
• If fault persists, replace SOLA