TRI-LITE HVLS SERIES CEILING FANS INSTALLATION INSTRUCTIONS / PLEASE READ AND SAVE THESE INSTRUCTIONS BEFORE YOU BEGIN Your kit should include all of the components shown below. FAN COMPONENTS CABLE DETAIL NOTE: HVLS blades are not shown in the assembly to allow greater detail of parts. See Figure 14 for finished assembly.
TRI-LITE HVLS SERIES FANS ELECTRICAL SAFETY ELECTRICAL HAZARD ! ! WARNING! Ignoring the following instructions can cause physical injury or death, or damage to the equipment. WARNING! Only qualified electricians are allowed to install the drive and connections to the motor! Never work on the drive, motor cable or motor when input power is applied.
TRI-LITE HVLS SERIES FANS DIFFERENT MOUNTING APPLICATIONS I BEAM MOUNTING NOTE: The following mounting applications are representations only and are subject to change without notice. Contact your Canarm sales representative for complete mounting instructions.
TRI-LITE HVLS SERIES FANS STANDARD MOUNT FIGURE 1 A Standard Mount package is used with all Tri-Lite HVLS Fans assemblies (except “Wood” Beam Mounting). See Figure 1. Standard drop mounts of approximately 1’, 2’ and 4’ are available. The package includes: (2) mfg “I” Beam clamps (2) mfg “I” Beam spacers (may or may not be required for assembly) (1) Upper Pivot Plate (1) Upper Pivot (pre-assembled) (1) Stem for 1’, 2’ and 4’ packages (4) Bolts, Nuts & Washers (1) Cable 5mm SS (Length 6.
TRI-LITE HVLS SERIES FANS INSTALLING THE EXTENSION FIGURE 5 1. Using a 7/8” wrench, fasten top plate of extension to the bottom plate of the standard mount using M14 bolts, nuts and washers. 2. Position the safety cable as per Figure 5, loop at both ends. 3. Using a 7/16” wrench, fasten the cable clamps 2 per end and as per typical cable clamp installation (Figure 3). Cable should be relatively snug.
TRI-LITE HVLS SERIES FANS GUY WIRES The package includes: (4) Cable 3mm SS (66’ length provided to equal 4 @ 16.5’) (8) Thimbles 6mm SS (16) Cable Clamps 3mm Extra hardware required: (4) Forged Eye Bolts M6-1.0 x 100mm (4) Nuts M6-1.0 (4) Nylocks Mg-1.0 (8) Washers Flat M6 I-Beam Nut Washer Eye Bolt Thimble Clamps Nylock Washer Guy Cable Fig.
TRI-LITE HVLS SERIES FANS INSTALLING GUY WIRES 1. 2. 3. 4. 5. FIGURE 11 Determine mounting position on ceiling and establish the angle between 45˚ - 60˚ for the cable. Determine correct location on the I Beam to drill 5/16” diameter hole for the eye bolt. For example, if fan is 3.3’ down from ceiling, cables should be mounted approximately 3.3’ away from fan. Using a 3/8” wrench, install eye bolt with nuts and washers in I Beam as per Figure 9.
TRI-LITE HVLS SERIES FANS FINAL STEPS FIGURE 14 IMPORTANT LEVELLING INSTRUCTIONS: After your fan is installed, check the level again by placing your level vertically on the side of the fan frame. If adjustment is needed slightly tighten the guy wire on the appropriate side. Once levelled your fan is installed and ready for electrical installation / connection. For proper electrical connection, please consult the motor wiring diagram (supplied with the motor).
TRI-LITE HVLS SERIES FANS RECOMMENDED MAINTENANCE SCHEDULE ! WARNING! TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: 1. No maintenance shall be done on the fan, mount or guy wires while it is in operation or powered. 2. No maintenance shall be done on the fan controller while powered unless the task involves reprogramming or troubleshooting the electrical system. 3.
TRI-LITE HVLS SERIES FANS RECOMMENDED MAINTENANCE SCHEDULE CONTINUED Control Panel Tri-Lite HVLS controls are variable frequency drives which provide soft start/stop, variable speed control and overload protection for the motors. The VFD also allows fan control to be automated and/or integrated with other systems. The controls come with a one year limited warranty.
TRI-LITE HVLS SERIES FANS RECOMMENDED MAINTENANCE CHECKLIST Fan Size: ____________________ Fan Size: ____________________ Fan Size: ____________________ Serial #: _____________________ Serial #: _____________________ Serial #: _____________________ Location: ____________________ Location: ____________________ Location: ____________________ Date Initials TRI-LITE HVLS-M (04_29_15) Date Initials Date Initials Page 11 of 13
TRI-LITE HVLS SERIES FANS LIMITATION OF WARRANTY AND LIABILITY The Tri-Lite HVLS fans are of industrial grade construction and should provide many years of virtually maintenance free use. Warranty duration is as follows: a) Air Foil Shaped Blade 1 year limited warranty b) Aluminum Alloy Hub 1 year limited warranty c) Gear Motor 1 year limited warranty d) VFD Control Panel 1 year limited warranty Canarm Ltd.
TRI-LITE HVLS SERIES FANS LIMITATION OF WARRANTY AND LIABILITY Canarm Ltd. reserves the right to make the final determination, based on its own evaluation of the components as to whether: • • • The problem in question is the result of a defect in design, workmanship or materials and not the result of error, misuse or abuse on the part of the customer as stated above. Whether the problem or defect is material and requires action under this warranty.