Specifications

InstallationandOperationManual(REVH) PVI6500/PVI7500

24
!
Fig2.3.8Utilityconfigurations
2.4ConnectionoftheACwiring
UseoneofthefollowingproceduresbelowtowiretheACconductors.
Open the circuit breaker box, switchoff and lockoutthe circuitbreaker box that willbe used to connect the inverter tothe
building.
WARNING!
Reconfirmthatthecircuitbreakertothegrid/utilityisswitchedOFFandlockedoutbeforeconnectingthepower
wiresfromthebreakertotheinverterACterminalblock.MeasuretheabsenceofvoltagewithanACvoltmeter.
WARNING!
Longwirescausevoltagedrop.TheacceptablerangeforACvoltagedropis1.5%ofnominal.Thevoltagedropin
excessof1.5%ofnominalACvoltageisanindicationthatlargersizewireshouldbeused.