InstallationandOperationManual(REVH) PVI6500/PVI7500

40
3seconds
Ifthegridtypeissetto240VACwithoutneutral,thenthedisplaywillbelookedasthefigureshownbelow.
3seconds
Three(3)secondslater,theLCDwillshowthevoltagesettingfortheinvertertodropthegridconnection.Thesettings
oftheVl
nHanditsclearingtimewillbedisplayed.TheVlnHsettingisthephasetoneutral(rms)highthresholdvoltagesettingatwhich
pointtheinverterdisconnectsitsoutputfromtheACpowergridwhenabnormallyhighphasetoneutralACvoltageisdetected.
Afterthesetting
oftheVlnHisdisplayed,thesettingoftheVlnLwillbedisplayedfor3seconds.
3seconds↓
3seconds↓
Three(3)secondslater,theinverterdisplaysthesettingoftheVacHwhichisthephasetophase(rms)highthresholdvoltage
settingatwhichpointthe
inverterdisconnectsitselffromthegridwhenabnormallyhighphasetophaseACvoltageisdetected.
Also,thesettingoftheclearingtimewhichisthetotaldurationoftimetodisconnecttheoutputfromtheACgridisdisplayed.
Thisdelayisnecessarytoavoidnuisancetrips.Afterthesettings
oftheVacHanditsclearingtime,thesettingsoftheVacLand
itsclearingtimewillbedisplayedforthree(3)seconds.ThedisplayVlnH/VlnLisonlyfor208/240/277VACwithneutralsetting,
VacH/VasLisonlyfor240or208withoutneutral,theywouldnotdisplayatthe
sametime.
3seconds↓
3seconds↓
Then the high and low threshold settings of the AC frequency and the associated clearing time will be shown for three (3)
seconds.WhentheACfrequencyexceedsthehighorlowthresholdsetting,theinverterwilldisconnectitsoutputfromtheAC
grid.

G r id Type
L 1 12 0V L 2 1 20 V
G r id Type
L 1 - L 2 2 4 0 V
V l - n H XXX . XV
C l r t < XXX C y c s
V l - n L X X X . X V
C l r t < X X X C y c s
V a c H X X X . X V
C l r t < X X X C y c s
V a c L X X X . X V
C l r t < X X X C y c s