Specifications

InstallationandOperationManual(REVH) PVI6500/PVI7500

49
assistanceiftherangeneedstobe
adjusted
VacL
TheACvoltageofmain utilityisbelowthe
lowerlimit.
VerifysettingforS201iscorrectfor
thegridvoltageapplied
‐MeasuretheACvoltageandcompare
tothevoltageontheinverterdisplay
‐ContactSolectriaRenewablesfor
assistanceiftherangeneedstobe
adjusted
FacH
ThefrequencyofACvoltageoftheutilityis
abovetheupperlimit.
Measurethefrequencyandcompare
tothefrequencyonthedisplay
‐ContactSolectriaRenewablesfor
assistanceiftherangeneedstobe
adjusted
FacL
ThefrequencyofACvoltageoftheutilityis
belowthelowerlimit.
Measurethefrequencyandcompare
tothefrequencyonthedisplay
‐ContactSolectriaRenewablesfor
assistanceiftherangeneedstobe
adjusted
VpvH
TheDCvoltageofPVarrayisabovetheupper
limit.
Turnofftheinverterdisconnect
‐MeasuretheVDCattheInverter
disconnectifover599VDCthesolar
arrayneedstobeinspected
‐Contactinstallingcompany
‐Donotturnontheinverteruntilthe
conditionisrepaired
Imax_AC
OvercurrentontheACside.
Theinverterwillcontinuetooperate
atalowercurrent
‐Ifmessageoccursfrequentlycontact
theinstallingcompany
InvTempMax
Theinternaltemperatureoftheinverter
exceededthesafeoperatinglimit.
Iftheinverterislocatedindirect
sunlightitmayneedtobeshaded
‐TheVDCinputmaybetoohigh
causingincreasedtemperature,reduce
VDCinput.
‐ContactinstallingcompanyorSolectria
Renewables
RelayOpen
RelayClose
Relaytestfailed.‐ContactinstallingcompanyorSolectria
Renewables
VacL1H
ThevoltagebetweenL1andneutralisoverthe
upperlimit.
VerifysettingforS201iscorrectfor
thegridvoltageapplied
‐MeasuretheACvoltageandcompare
tothevoltageontheinverterdisplay
‐ContactSolectriaRenewablesfor
assistanceiftherangeneedstobe
adjusted
VacL1L
ThevoltagebetweenL1andneutralisunder
thelowerlimit.
VerifysettingforS201iscorrectfor
thegridvoltageapplied
‐MeasuretheACvoltageandcompare
tothevoltageontheinverterdisplay
‐ContactSolectriaRenewablesfor
assistanceiftherangeneedstobe
adjusted
VacL2H
ThevoltagebetweenL2andneutralisoverthe
upperlimit.
VerifysettingforS201iscorrectfor
thegridvoltageapplied
‐MeasuretheACvoltageandcompare
tothevoltageontheinverterdisplay
‐ContactSolectriaRenewablesfor