Specifications

InstallationandOperationManual(REVH) PVI6500/PVI7500

50
assistanceiftherangeneedstobe
adjusted
VacL2L
ThevoltagebetweenL2andneutralisunder
thelowerlimit.
VerifysettingforS201iscorrectfor
thegridvoltageapplied
‐MeasuretheACvoltageandcompare
tothevoltageontheinverterdisplay
‐ContactSolectriaRenewablesfor
assistanceiftherangeneedstobe
adjusted
MOVFault,AC
Highvoltageprotectionfunctionfailedonthe
ACside.
VerifyMOVappearanceisOK
‐ContactSolectriaRenewables
MOVFault,DC
Highvoltageprotectionfunctionfailedonthe
DCside.
VerifyMOVappearanceisOK
‐ContactSolectriaRenewables
GFDI TheGFDIFuseisopenorblown. UseDMMtoverifyGFDIisopen
contactinstallingcompanytoinspect
andrepairthearray
‐Replacefusewithsametypeand
rating
DCInjectCurH
ToomuchDCcurrentinjectedintotheACgrid
isdetected.
Turnoff theinverterandrestart.
‐IftheerrorreoccursContactinstalling
companyorSolectriaRenewables
VdcbusH
InternalDCbusvoltageisabovetheupper
limit.
Turnoff theinverterandrestart.
‐IftheerrorreoccursContactinstalling
companyorSolectriaRenewables
InternalCOMM
Internalcommunicationfailed.
Turnoff theinverterandrestart.
‐IftheerrorreoccursContactinstalling
companyorSolectriaRenewables
Watchdog Internalwatchdogfunctiontriggered. Turnoff theinverterandrestart.
‐IftheerrorreoccursContactinstalling
companyorSolectriaRenewables
IdcTest Offsetcheckforgridmonitoringfailed Turnoff theinverterandrestart.
‐IftheerrorreoccursContactinstalling
companyorSolectriaRenewables
Offset
TheDCinjectioncurrentmonitoringfunction
failed.
Turnofftheinverterandrestart.
‐IftheerrorreoccursContactinstalling
companyorSolectriaRenewables
Temp.Sensor Offsetcheckforgridmonitoringfailed. Turnoff theinverterandrestart.
‐IftheerrorreoccursContactinstalling
companyorSolectriaRenewables
RAMTest
Theinternaltemperaturesensorfailed.
Turnoff theinverterandrestart.
‐IftheerrorreoccursContactinstalling
companyorSolectriaRenewables
EEPROMTest
Memoryfailed
Turnoff theinverterandrestart.
‐IftheerrorreoccursContactinstalling
companyorSolectriaRenewables
SystemError
EEPROMtestfailed.
Turnoff theinverterandrestart.
‐IftheerrorreoccursContactinstalling
companyorSolectriaRenewables
VersionError
Thesystemfailed.
Turnoff theinverterandrestart.
‐IftheerrorreoccursContactinstalling
companyorSolectriaRenewables
CPUDeltaFac
CPUDeltaVac
CPUDeltaGFDI
CPUDeltaIdc
Thefirmwareversionisnotcorrect.
Internalmeasurementcomparisonerroror
defectivehardware
Turnoff theinverterandrestart.
‐IftheerrorreoccursContactinstalling
companyorSolectriaRenewables