Specifications
InstallationandOperationManual(REVH) PVI6500/PVI7500
68
Noiselevelatfullload <47db(A)at1m
Mechanical
Outdoorenclosure NEMA3R,Rainproof
Cooling Coolingfan
DCInputterminals Acceptswiresizeof#10to#6AWG
ACOutputterminals Acceptswiresizeof#10to#6AWG
DCconduitconnectionaccess 1”knockout(1.38")/¾”knockout(1.06")
ACconduitconnectionaccess 1”knockout(1.38")/¾”knockout(1.06")
Communicationconnection ¾”knockout(1.06")/½”knockout(0.79")
Mechanical
Weight/Shippingweight 41kg/47kg(90lb/104lb)
Dimensions(HxWxD) 28.8x17.2x8.2"(732x438x208mm)
Shippingdimensions(HxWxD) 33.1x21.65x13.98"(840x550x355mm)
CommunicationInterface
Communication RS232andRS485
Communicationprotocol MODBUS
LCDdisplay Yes
LEDindicators Red/Green/Yellow
Positivegroundinverters
Name‐Partnumber PVI6500 PVI7500
Modelname PVI6500‐PG PVI7500‐PG
Certifications
UL1741,FCCPart15B,IEEE1547,IEEEC62.41.2,IEEEC37.90.1,CSA22.2#107.1
*Factorysettingscanbeadjustedwiththeapprovaloftheutility.Thisunitisprovidedwithadjustabletriplimitsandmay
beaggregatedabove30kWonasinglePointofCommonCoupling.
Adjustablevoltage,FrequencyandReconnectionSettings
Setting Range Default Accuracy
Over‐voltage(%) 108.75~110 110 ±1
Under‐voltage(%)
85~90 88 ±1
Over‐voltageReconnectvoltage*(%)
105.83~110 105.83 ±1
Under‐voltageReconnectvoltage*(%)
85~91.67 91.67 ±1
Over‐frequency(Hz)
60.4~61 60.49 ±0.02
Under‐frequency(Hz) 57~59.8 59.31 ±0.02
Over‐voltageclearingtime(cycle)
59~120 59 ±1
Under‐voltageclearingtime(cycle)
119~300 119 ±1
Over‐frequencyclearingtime(cycle)
9~12 9 ±1
Under‐frequencyclearingtime(cycle)
9~18000 9 ±1
Setting Range Default Accuracy
AChigh‐voltagelimit(%)
100~110 109 ±1
Reconnectdelay**(s)
10~600 20 ±0.01
* ThedefaultvaluesarewithintheRangeBofANSIC84.1
** Onceagridfailure,theinverterwaits300secondsbeforethenextconnectiontothegrid.