OWNER / May 16, 2013 28 23 00 - 10 Video Surveillance System
2.01 GENERAL
A. Contractor Responsibility
1. All products not provided by OWNER shall be new and unused, and shall be of
manufacturer’s current and standard production.
2. Where two or more equipment items of the same kind are provided, all shall be identical
and provided by the same manufacturer.
3. Drawings and Specifications indicate major system components, and may not show every
component, connector, module, or accessory that may be required to support the operation
specified. Contractor shall provide all components needed for complete and satisfactory
operation.
B. Product Availability
1. Contractor, prior to submitting a proposal, shall determine product availability and
delivery time, and shall include such considerations into his proposed Contract Time.
2. Certain products specified may only be available through factory-authorized dealers and
distributors. Contractor shall verify his ability to procure the products specified prior to
submitting a proposal.
C. Wire And Cable
3. General: Provide all wire and cable required to install all systems and components. Wire
and cable shall be sized to provide minimum voltage drop and minimum resistance to the
devices being supplied.
4. All cables shall be specifically designed for their intended use (direct burial, aerial, etc.).
5. Comply with equipment manufacturers’ recommendations for wire and cable.
6. Color codes shall be consistent in cables used for the same purpose.
7. Comply with all applicable codes and ordinances.
D. Conduit And Raceway Systems
1. General: OWNER shall approve The placing of surface mounted conduit on the exterior
of any building prior to its installation.
2. Interior Conduit:
a. Electrical Metallic Tubing (EMT)
b. Flexible Metal Conduit
c. Provide fittings and connectors as required for installation of EMT or flexible
conduit.
3. Surface Raceways:
a. Sheet metal channel with fitted cover, suitable for use as surface metal raceway,
WIREMOLD or approved equal.
b. Provide fittings, elbows, connectors and covers designed for use with each raceway
system.
4. Exterior Conduit: (any of the following as determined by local code requirements):
a. Rigid Steel Conduit
b. Rigid Aluminum Conduit
c. Rigid Nonmetallic Conduit (only if buried 18" below ground surface).
d. Intermediate Metal Conduit
e. Provide rain-tight fittings and connectors as required for installation of exterior
conduit.
5. Exterior Flexible Conduit:
a. Liquidtight Flexible Conduit: Flexible metal conduit with PVC jacket.