Product Brochure
- 16 -
Low Prole
The Endura® Lo-PRO is installed on oor. Ensure you design/locate
the grease interceptor so as to allow for maintenance. Placement
should allow the cover to be easily removed for cleaning. A minimum
clearance of only 6 inches is required above the top of the Grease
Interceptor to allow removal of the internal baes for a complete
cleanout.
CAUTION: CLEARANCE REQUIRED
6” clearance above the grease interceptor required to
remove the baes for cleaning and maintenance.
• Flow Control Device
• Vented Waste
• Minimum Clearance 6”
• Grease Interceptor
• Air Intake
• Sink
• Cleanout required in
most jurisdictions
• Cleanout required in
most jurisdictions
CAUTION
• Floor Below - Multiple Fixture Installation
• Floor Below - Extended Capacity, Multiple Fixture Installation
One interceptor serving multiple xtures is recommended
only when the xtures are located close together (max 25 ft of
developed pipe run). In such installations, each xture should
be individually trapped and back-vented.
• XL Grease
Interceptor
• External Flow Control (Optional)
required for PDI installations
(No internal ow control installed)
• Vented Waste
• Internal Flow
Control and Bae
• Air Intake
• Sink
Ontario Can. Plumbing Code 7.4.4.3 (9) Typical Installation
Typical Installation
PDI Installation - * If more
than 8 ft (2.4 m), a secondary
ow control must be installed
preceding the grease interceptor
to maintain ow velocities in the
system.
A secondary Flow Control
is required if the height of
verticle discharge exceeds
5-feet.
The secondary ow control
shall be located no more
than 5-feet above the
interceptor invert.
PDI Installation - * If more
than 8 ft (2.4 m), a secondary
ow control must be installed
preceding the grease interceptor
to maintain ow velocities in the
system.
Internal Flow Control
Installed
Ontario Can. Plumbing Code 7.4.4.3 (9) Typical Installation
Typical Installation
A secondary Flow Control is
required if the height of verticle
discharge exceeds 5-feet.
The secondary ow control
shall be located no more
than 5-feet above the
interceptor invert.
• Flow Control Device
• Vented Waste
• Grease Interceptor
• Air Intake
• Sink
One interceptor serving multiple xtures is recommended only when the xtures
are located close together (max 25 ft of developed pipe run). In such installations,
each xture should be individually trapped and back-vented.
• Cleanout required in
most jurisdictions