Brochure

- 14 -
Typical Installation
• Flow Control Device
Vented Waste
Minimum Clearance 15” / 21”
• Grease Interceptor
• Air Intake
• On Floor
• Semi Recessed Option
• Sink
CAUTION
CAUTION: CLEARANCE REQUIRED
15” clearance (21” for 50GPM model) to remove the baes for
cleaning and maintenance.
• In Floor - Extended Capacity
When backlling in-oor, the interceptor must have both the
cover tted and be lled with water to the inlet/outlet level.
This will ensure the tank itself will not move during backlling,
pouring and/or oor nishing. When backlling in particular, care
should be taken to do so evenly around the unit and with light
manual pressure only.
Ensure that the interceptor is clearly identied to ooring
contractors to prevent it from being covered with ooring
material. Taping cardboard to the cover is generally eective.
When backlling in-oor, the interceptor must
have both the cover tted and be lled with water
to the inlet/outlet level. This will ensure the tank
itself will not move during backlling, pouring and/
or oor nishing. When backlling in particular, care
should be taken to do so evenly around the unit and
with light manual pressure only.
Ensure that the interceptor is clearly identied to
ooring contractors to prevent it from being covered
with ooring material. Taping cardboard to the cover
is generally eective.
• Flow Control Device
• XL Grease Interceptor
Vented Waste
• External Flow Control (Optional)
required for PDI installations
Minimum Clearance
15” / 21”
Vented Waste
• Air Intake
• Grease Interceptor
• Internal Flow Control
and Bae
• Air Intake
• Cleanout (recommended)
• Sink
• Sink
CAUTION
CAUTION
CAUTION
CAUTION
CAUTION
CAUTION
CAUTION: CLEARANCE REQUIRED
15” clearance (21” for 50GPM model) above the grease interceptor
is required to remove the baes for cleaning and maintenance.
CAUTION: CLEARANCE REQUIRED
Locate the interceptor so as to allow for accessibility
when conducting maintenance and regular cleaning.
Set the interceptor on a rm, level surface ensuring tank
is equally supported.
6” Modular risers available where deeper installation
is necessary to accommodate existing drainage.
- Stackable up to 3 sets (18” Total)
- 3920AX6 (20/25gpm) and 3935AX6 (35/50gpm)
• In Floor
CAUTION: CLEARANCE REQUIRED
• Cleanout required in
most jurisdictions
• Cleanout required in
most jurisdictions
Do Not Exceed 25 ft (7.6 m)
(For PDI Format Installation)
Do Not Exceed 25 ft (7.6 m)
(For PDI Format Installation)
Do Not Exceed 25 ft (7.6 m)
(For PDI Format Installation)
* Above grade installation
preferred
*
Risers available where deeper installation is
necessary to accommodate existing drainage.
- 35” or 18” Cut-to-length Riser Pair - Max Extension 72”
- Full accessories & instructions supplied
- Robust, Airtight, Watertight
- 100% recompounded riser, Integral guidelines for cutting
- PN: 35” - 40100AX35 / 18” - 40100AX18