Brochure

- 15 -
Low Prole
The Endura Lo-PRO is installed on oor. Ensure you design/locate
the grease interceptor so as to allow for maintenance. Placement
should allow the cover to be easily removed for cleaning. A minimum
clearance of only 6 inches is required above the top of the Grease
Interceptor to allow removal of the internal baes for a complete
cleanout.
CAUTION: CLEARANCE REQUIRED
6” clearance above the grease interceptor required to
remove the baes for cleaning and maintenance.
• Flow Control Device
Vented Waste
Minimum Clearance 6”
• Grease Interceptor
• Air Intake
• Sink
• Cleanout required in
most jurisdictions
• Cleanout required in
most jurisdictions
CAUTION
• Floor Below - Multiple Fixture Installation
• Floor Below - Extended Capacity, Multiple Fixture Installation
One interceptor serving multiple xtures is recommended
only when the xtures are located close together (max 25 ft of
developed pipe run). In such installations, each xture should be
individually trapped and back-vented.
• XL Grease
Interceptor
• External Flow Control (Optional)
required for PDI installations
(No internal ow control installed)
Vented Waste
• Internal Flow
Control and Bae
• Air Intake
• Sink
Ontario Can. Plumbing Code 7.4.4.3 (9) Typical Installation
Typical Installation
PDI Installation - * If more
than 8 ft (2.4 m), a secondary
ow control must be installed
preceding the grease interceptor
to maintain ow velocities in the
system.
A secondary Flow Control
is required if the height of
verticle discharge exceeds
5-feet.
The secondary ow control
shall be located no more
than 5-feet above the
interceptor invert.
PDI Installation - * If more
than 8 ft (2.4 m), a secondary
ow control must be installed
preceding the grease interceptor
to maintain ow velocities in the
system.
Internal Flow Control
Installed
Ontario Can. Plumbing Code 7.4.4.3 (9) Typical Installation
Typical Installation
A secondary Flow Control is
required if the height of verticle
discharge exceeds 5-feet.
The secondary ow control
shall be located no more
than 5-feet above the
interceptor invert.
• Flow Control Device
Vented Waste
• Grease Interceptor
• Air Intake
• Sink
One interceptor serving multiple xtures is recommended only when the xtures
are located close together (max 25 ft of developed pipe run). In such installations,
each xture should be individually trapped and back-vented.
• Cleanout required in
most jurisdictions