Installation Instructions PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Catalog Numbers 2711P-Kxxxx, 2711P-Txxxx, 2711P-Bxxxx, 2711P-RDxxxx, 2711PC-T10C4D1 Topic Page Important User Information 2 Environment and Enclosure 3 Hazardous Locations 4 Wiring and Safety Guidelines 8 About the PanelView Plus 700 to 1500 Terminals 8 Parts List 10 Required Tools 10 Install the Terminal 10 DC Power Connections 16 AC Power Connections 20 Battery Precaut
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 3 Environment and Enclosure ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 m (6561 ft) without derating. The terminals are intended for use with programmable logic controllers.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Hazardous Locations This equipment is suitable for these locations: • • • • Class I, Division 2 Groups A, B, C, D Class II, Division 2 Groups F, G Class III Ordinary, nonhazardous locations only The following statement applies to use in hazardous locations. WARNING Explosion Hazard • Substitution of components may impair suitability for hazardous locations.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 5 Environnements dangereux Cet équipement ne peut être utilisé que dans les environnements suivants : • • • • Classe I, Division 2, Groupes A, B, C, D Classe II, Division 2, Groupes F, G Classe III ou environnements non-dangereux La mise en garde suivante s’applique à une utilisation en environnement dangereux.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules USB Ports All PanelView Plus and PanelView Plus Compact terminals contain universal serial bus (USB) ports that comply with hazardous location environments. This section details the field-wiring compliance requirements and is provided in accordance with the National Electrical Code, article 500.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 7 Application Information Per the National Electrical Code the circuit parameters of nonincendive field wiring apparatus for use in hazardous locations shall be coordinated with the associated nonincendive field wiring apparatus such that their combination remains nonincendive. The PanelView Plus terminals and the USB peripheral device shall be treated in this manner.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Wiring and Safety Guidelines Use publication NFPA 70E, Electrical Safety Requirements for Employee Workplaces, IEC 60364 Electrical Installations in Buildings, or other applicable wiring safety requirements for the country of installation when wiring the devices. In addition to the NFPA guidelines: • • • • connect the device and other similar electronic equipment to its own branch circuit.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 9 Modular Components Communication Module Power Input, AC or DC Logic Module Display Module Ethernet Port USB Ports CompactFlash Card Slot Serial Port If the modules are ordered separately, attach the logic and communication module to the display module before panel installation. See the instructions shipped with each module.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Parts List These items are shipped with the terminals: • • • • Power terminal block Mounting clips FactoryTalk View software preloaded Installation instructions and panel cutout template Required Tools These tools are required for panel installation: • Panel cutout tools • Small, slotted screwdriver • Torque wrench (lb•in) Install the Terminal Before installing the terminal in a panel, review the following topic
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 11 Panel Cutout Dimensions Use the full size template shipped with your terminal to mark the cutout dimensions. Terminal Type Height, mm (in.) Width, mm (in.) 700 Keypad or Keypad and Touch 167 (6.57) 264 (10.39) 700 Touch 154 (6.08) 220 (8.67) 1000 Keypad or Keypad and Touch 224 (8.8) 375 (14.75) 1000 Touch 224 (8.8) 305 (12.00) 1250 Keypad or Keypad and Touch 257 (10.11) 390 (15.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules This gasket forms a compression type seal. Do not use sealing compounds. Sealing Gasket 3. Install the legend strips before installing the terminal if you are using keypad legend strips on keypad terminals. Be careful not to pinch the legend strip during installation. 4. Place the terminal in the panel cutout. 5. Slide the ends of the mounting clips into the slots on the terminal.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 13 7. Tighten the mounting clip screws to a torque of 0.90…1.1 N•m (8…10 lb•in) by using the specified torque sequence, making sure not to overtighten. 1 4 1 4 Clips 5 3 1 6 3 6 Clips 8 8 Clips 3 2 4 2 6 7 4 5 ATTENTION 2 Tighten the mounting clips to the specified torque to provide a proper seal and prevent damage to the product.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules The illustration shows product dimensions for the PanelView Plus and PanelView Plus Compact 1000 touch only terminals. The other size terminals look similar. Measurements are in mm (in.). 1000 Terminal Dimensions Keypad or Keypad & Touch 248 (9.77) 399 (15.72) a 55 (2.18) Display to Logic Module b 83 (3.27) Display to Comm Module b a Touch Screen 329 (12.97) a 55 (2.18) Display to Logic Module b 83 (3.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 15 Ethernet Wiring Use Belden 7921A shielded Ethernet Category 5e cable according to TIA 568-B.1 and RJ45 connector according to IEC 60603-7 for compliance with Marine emissions limits and European Union 89/336/EEC EMC Directive. The maximum cable length between the terminal’s Ethernet port and a 10/100 Base-T port on an Ethernet hub (without repeaters or fiber) is 100 m (328 ft).
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Follow these steps to remove the terminal block. 1. Loosen the two screws that secure the terminal block. 2. Gently pull the terminal block away from the connector. 3-position AC or DC Terminal Block 2-position DC Terminal Block (series E or later) Follow these steps to install the terminal block. 1. Reattach the terminal block to the connector until seated. 2.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 17 External Power Supply For Non-isolated DC Terminals TIP To identify non-isolated DC logic modules refer to the PanelView Plus Terminals user manual, publication 2711P-UM001. Use a single, 24V DC power supply to power each PanelView Plus device, such as catalog number 2711P-RSACDIN. Using a separate, isolated and ungrounded source to power each terminal prevents ground loop currents from damaging the terminals.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules External Power for Isolated DC Terminals TIP Isolated DC logic modules are identified by catalog number 2711P-RPxDx. Use an SELV or PELV 24V DC power supply, such as catalog number 2711P-RSACDIN, to power the isolated DC PanelView Plus terminal. The isolated DC terminals may be powered by the same power source as other equipment.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 19 Connect DC Power WARNING Explosion Hazard - Do not disconnect equipment unless power has been switched off and area is known to be nonhazardous. Disconnect all power before installing or replacing components. Failure to disconnect power may result in electrical shock or damage to the terminal. Follow these steps to connect the terminal DC power. 1. Verify that the terminal is not connected to a power source. 2.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules AC Power Connections PanelView Plus devices with an integrated AC power supply have these power ratings: • 85…264V AC (47…63 Hz) • 160V A max The input power terminal block supports these wire sizes. Wire Specifications for AC Input Power Terminal Block Stranded or solid (1) Gauge(1) Single-wire Gauge Terminal Screw Torque 22…16 AWG 22…14 AWG 0.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 21 Connect AC Power WARNING Explosion Hazard - Do not connect or disconnect equipment while circuit is live unless area is known to be nonhazardous. Disconnect all power before installing or replacing components. Failure to disconnect power may result in electrical shock and/or damage to the terminal. ATTENTION Improper wiring of power terminals may result in voltage at the communication connector shells.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Battery Precautions When you connect or disconnect the battery an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed and the area is nonhazardous before proceeding.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 23 6. Locate the battery on the circuit board. Lift up the edge of the battery indicated by the arrow. 7. Remove the battery by lifting up the side of the battery. 8. Insert the new battery. IMPORTANT Use only replacement battery catalog number 2711P-RY2032. 9. Reattach the logic module by aligning the two connectors on the bottom of the module with the connectors on the terminal. 10.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 12. Reattach the communication module, if necessary, and tighten the four screws to a torque of 0.58 N•m (5…7 lb•in). This product contains a hermetically sealed lithium battery which may need to be replaced during the life of the product. At the end of its life, the battery contained in this product should be collected separately from any unsorted municipal waste.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 25 The table shows indicator states if the terminal powers on and stops during startup. Indicator States If the Terminal Stops During Startup Fault (Red) Indicator Blinking(1) On(2) Comm (Green) Indicator Description Off Last firmware download failed. Reload firmware using Firmware Upgrade Wizard (FUW) utility. Blinking EBC boot loader firmware failed or is missing.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Startup Information Messages Startup information messages display in a specific sequence on the terminal during startup and typically display for a few seconds. These messages do not require that you perform any action. Message # Message Description 37 Video Initialized Configures and initializes the graphics video system. 30 Watchdog Test Tests the watchdog circuitry to verify system integrity.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 27 Startup Error Messages When an error occurs, the terminal displays an error number with a text message. The word ERROR! appears under the message in different languages. # Displayed Message ERROR! FEHLER! ERREUR! ERRORE! Error # Message Description Recommended Corrective Action 1 RAM Test RAM test failure. Reset the terminal. If error persists, reseat the SO-DIMM RAM module.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Specifications PanelView Plus Terminals - 2711P-Kxxxx, 2711P-Txxxx, 2711P-Bxxxx, 2711P-RDxxxx, 2711PC-Txxxx Attribute Value Display Display type Color active matrix, thin film transistor (TFT), liquid crystal display (LCD) Display size 700 1000 1250 1500 6.5 in. 10.4 in. 12.1 in. 15 in. Display area (WxH) 700 1000 1250 1500 132 x 99 mm (5.2 x 3.9 in.) 211 x 158 mm (8.3 x 6.2 in.) 246 x 184 mm (9.7 in x 7.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 29 PanelView Plus Terminals - 2711P-Kxxxx, 2711P-Txxxx, 2711P-Bxxxx, 2711P-RDxxxx, 2711PC-Txxxx Weight, Approx. for base configured unit without communication module 700 keypad, or keypad and touch 1.9 kg (4.2 lb) 700 touch 1.7 kg (3.8 lb) 1000 keypad, or keypad and touch 2.9 kg (6.3 lb) 1000 touch 2.6 kg (5.7 lb) 1250 keypad, or keypad and touch 3.4 kg (7.6 lb) 1250 touch 3.2 kg (7.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules Certifications Certification (1) c-UL-us UL Listed Industrial Control Equipment, certified for use in US and Canada. See File E10314.
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 31 Publication 2711P-IN001I-EN-P - November 2009
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.