50 Power Connections
Functional Earth Connection
PanelView Plus devices with a dc power input have a functional earth
terminal that you must connect to a low-impedance earth ground.
The 700 to 1500 terminals have the functional earth ground
connection on the rear of the display module.
The 400 and 600 terminals have the functional earth ground
connection on the power input terminal block.
The functional earth terminal requires a minimum wire gauge.
Functional Earth Wire Specifications for DC Power
On most PanelView Plus dc terminals, the functional earth terminal is
internally connected to the dc- terminal within the product.
The PanelView terminals have isolated and nonisolated
communication ports.
Refer to Chapter 7 for information on communication port Isolation.
IMPORTANT
The functional earth connection to ground is mandatory. This
connection is required for noise immunity, reliability, and
Electromagnetic Compliance (EMC) with the European Union
(EU) EMC directive for CE-mark conformance.
Terminal FE Symbol Wire Type Wire Gauge Terminal Screw Torque
400 and 600
Stranded or solid Cu 90 °C (194 °F)
14…12 AWG 0.45…0.56 Nm (4…5 lb-in)
700 to1500 14…10 AWG 1.13…1.36 Nm (10…12 lb-in)
ATTENTION
Damage or malfunction can occur when a voltage potential
exists between two separate ground points. Make sure the
terminal does not serve as a conductive path between ground
points at different potentials.
IMPORTANT
For more information, refer to Wiring and Grounding Guidelines
for PanelView Plus Devices, publication 2711P-TD001.