Specifications
LV5692P, LV5693P Application Note 
http://onsemi.com 
28 
[CTRL1/2/3 input] 
CTRL1 accepts three input  values (L/M/H)., 
CTRL2 accepts four input values(L/M1/M2/H) 
and  CTRL3  accepts  two  values(L/H). 
CTRL1/2/3  have  a  pull-down resistance,  and 
this resistance value is 400kΩ.   
Logic table is shown on page7. 
[VCC/VCC1] 
VCC1 voltage must be higher than VCC-0.7V, 
because  internal  diode  between  VCC  and 
VCC1 becomes positively biased. This internal 
diode cannot be used  to supply current from 
VCC  to  VCC1  because  this  is  used only  for 
ESD protection purpose. 
[Protection] 
Thermal Shutdown 
To  protect  the  device  from  overheating  a 
thermal  shutdown  circuit  is  included.  If  the 
junction  temperature  reaches  approximately 
175 ℃ (typ),  all  outputs  are  turned  off 
regardless  of  CTRL  state.  Outputs  remain 
disabled  until  the  junction  temperature drops 
below 145℃(typ)(automatic restoration). 
The  thermal  shutdown  circuit  does  not 
guarantee  the  protection  of  the  final  product 
because it operates out of maximum rating 
(exceeding Tjmax=150℃). 
Current Limiting 
When the each output becomes in over load 
condition, the device limits the output current. 
All outputs are  also protected against  short 
circuit by fold back current limiter. 
Overvoltage 
The device is protected against load dump. 
When VCC voltage exceeds 21V, the device 
detects over voltage condition and turns all the 
outputs off except VDD to protect the device. If 
VCC  voltage  gets  below  21V,  outputs  are 
automatically restored.   
TEST Procedure 
Line regulation 
Line regulation is defined as the maximum 
change in output voltage as the input voltage 
is  varied  through  the  specified  range. It  is 
measured by changing the input  voltage and 
measuring the minimum/maximum voltage  of 
the  output.  Line  regulation  is  defined  as  the 
difference between maximum and  minimum 
voltage. 
Load regulation 
Load  regulation  is  defined  as  the  maximum 
change in output voltage as the load current is 
varied  through  the  specified  range.  It  is 
measured  by  changing  the  load  current  and 
measuring the minimum/maximum voltage  of 
the output. Load regulation is defined as the 
difference between maximum and  minimum 
voltage. 
Dropout voltage 
Dropout  voltage  is  defined  as  the  minimum 
input-to-output  differential  voltage  at  the 
specified load current required by the regulator 
to keep the  output voltage in regulation. It is 
measured by  reducing input voltage  until the 
output voltage drops below the nominal value. 
Ripple rejection 
Ripple rejection is defined as the ratio of input 
ripple amplitude versus that of output. 










