2.2 Main board: description of the terminals
Below is the wiring diagram for the MPXPRO main board in the version
with 5 relays. The connectors are screen printed to simplify the electrical
connections.
Terminal Description
30 GND Multifunction analogue/digital input
• NTC, PTC, PT1000, NTCL243 probe
• Multifunction digital input
32 S5/DI2
33 S4/DI1
34 GND
NTC/PTC/PT1000/NTCL243 probes
35 S3
36 S2
37 S1
Note:
• Depending on the model, the main board may have two open
collector/PWM analogue outputs for connecting:
1. PWM1: phase - cutting controllers (e.g. MCHRTF****) for inductive loads
(e.g. evaporator fans with inductive motors for optically-isolated
control);
2. PWM2: SSR relay for the anti-sweat heaters on the display cases;
• The devices with 4 to 20 mA or 0 to 10 Vdc output connected to input
S7 cannot be powered directly from the MPXPRO. They therefore
require an appropriate external power supply.
Important:
• The type of input connected to each probe in the same group can be
confi gured by just one parameter. For each group 1(S1,S2,S3)-2(S4,S5)-
3(S6)-4(S7), there is just one parameter that defi nes the type of input,
and consequently this must be the same for all the probes in the same
group. For group 2, S4 and S5 can be confi gured as probes yet operate
as digital inputs.
• All the contacts should be galvanically insulated by adding further relays
for each contact. The digital inputs must not be connected in parallel,
otherwise the board may be damaged.
Note: before performing any operations on the control board,
disconnect the main power supply by turning the main switch in
the electrical panel OFF.
5Vdc
S7/
DI4
GND VLGNDDI5 GND
M.S.N.
Tx/Rx
T.U.I.
Tx/Rx
Tx/Rx+ Tx/Rx-
S6/
DI3
S5/
DI2
AC 115-230 V
200 mA max
(*) = R2 and R4 only for 5 relays models
MX30P485**
6 (4) A N.O.
6 (4) A N.C.
6 (4) A N.O.
6 (4) A N.C.
EN60730-1
R1
R1
R5
10 (10) A N.O.
R2
R2 (*)
10 (2) A N.O.
R3
R3
6 (4) A N.O.
R4
R4 (*)
R5
LN
8 9
NO NC C
10 11 12
NO C
13 14 15
NCNO C
16
36
S2S1 S3
35
1718
12 VPWM1PWM2
19
324
NO NC CNL
67
CNO
51
37
33
S4/
DI1
GND
3234 30 2931 25 24262728 2223 2021
-10T50
MX30**H**
Power Supply
AC 115-230 V
200 mA max
Expansion board:
- 0 to10 Vdc Analog output MX3OPA10**
- PWM driver MX3OPPWM**
- E
2
V driver MX3OPSTP**
PROG. KEY
CLOCK and
SERIAL INT.
Mounted on
MX30S*****
Maximum currents with removable vertical connectors cod. MX30***(C,I,O)**.
For more details, please refer to the technical leaets.
MXOPZKEYA0 (with rel. 2.x)
IROPZKEYA0 (with rel. 1.x)
To be used only with
control switch o
(no Power Supply)
MX3OP48500
(only for slave models MX30S*****)
Fig. 2.f
Terminal Description
1 L Power supply:
230 Vac, 50mA max. (mod. MX30***E**)
115 Vac, 100mA max. (mod. MX30***A**)
2N
3 NO Relay 1: EN60730-1: 6(4)A N.O.,6(4)A N.C. 2(2)A C.O.
UL: 6A res 240Vac N.O. / N.C.
1/2Hp 240Vac N.O. 1/6 Hp 120Vac N.O.
4NC
5C
6 NO Relay 2: EN60730-1: 10(10)A N.O.
UL: 10A res 1Hp 240/120 Vac N.O.
only models
with 5 relays
7C
8NO
Relay 3: EN60730-1: 10(2)A N.O.
UL: 10A res 240Vac
9NC
10 C
11 Not used
12 NO Relay 4: EN60730-1: 6(4)A N.O.
UL: 6A res 240Vac; 1/2Hp 240Vac
1/6Hp 120Vac
only models
with 5 relays
13 C
14 NO Relay 5: EN60730-1: 6(4)A N.O., 6(4)A N.C.
UL: 6A res 240Vac N.O. / N.C.
1/2Hp 240Vac N.O; 1/6Hp 120Vac N.O.
15 NC
16 C
17 +12V Power supply
18 PWM1 Open collector output PWM1: 12Vdc, 20mA MAX
19 PWM2 Open collector output PWM2: 12Vdc, 20mA MAX
20 Tx/Rx- Connection to RS485 network supervisory - CAREL
and Modbus® protocol - for Master controller only
(use shielded cable)
21 Tx/Rx+
22 GND
23 M.S.N Tx/Rx Connection to Master/Slave tLAN (Master Slave
Network). Use shielded cable.
26 GND
24 Tx/Rx
tLAN connection for user terminals and remote
display
25 VL
26 GND
26 GND
Multifunction digital input
27 DI5
28 DC 5 V Multifunction analogue/digital input
• NTC, PTC, PT1000, NTCL243 probe
• 0 to 5 Vdc ratiometric probe
• 0 to 10 Vdc analogue input
• 4 to 20 mA analogue input
• Multifunction digital input
29 S7/DI4
30 GND
28 DC 5 V Multifunction analogue/digital input
• NTC, PTC, PT1000, NTCL243 probe
• 0 to 5 Vdc ratiometric probe
• Multifunction digital input
30 GND
31 S6/DI3