User manual
20
ENG
MPXPRO - + 0300055EN rel. 1.3 07/03/13
3.2 Keypad
Setting Function
Front keypad controls Display when setting / notes
Duration
Set point Temperature set point
Value on display fl ashing
/
Set value
Save set point and return to standard display
Access the parameters (program-
ming level)
Type F parameters (fre-
quent)
5 s The fi rst type F parameter is displayed
Type C (confi guration) or A
(advanced) parameters
&
5 s
/
Enter password (22 for confi guration level and 33 for advanced level)
Confi rm the password, the fi rst type C or A parameter is displayed
Output from the livello program-
ming
5 s The changes are saved
Defrost
Local defrost
5 s dFb : activate defrost dFE : deactivate defrost
Multiplexed defrost (Master
only)
&
5 s dFb : activate defrost dFE : deactivate defrost
Auxiliary functions
Continuous cycle
&
5 s
ccb : activate continuous cycle (see paragraph 6.6)
ccE : deactivate continuous cycle
AUX output
Activate/deactivate auxiliary output
Network functions (only for
Master)
Copy parameters from
Master to Slave
&
5 s
/
Enter password (default 66)
See paragraph 3.6 : “Copy parameters from Master to Slave”
Display network unit status
from Master
& &
Select Slave: see paragraph 3.5 : “Display Slave controller status from
Master terminal”
Set the default parameters
(restore parameters)
Set default parameters (*)
on power-up
If 0 is displayed press set to continue
Alarms
Display alarm log
&
5 s
/
Enter password (default 44)
See paragraph 9.3: “Display alarm log”
Manual alarm reset
&
5 s “rES” indicates the alarm has been reset
Mute buzzer and disable
alarm relay
HACCP HACCP menu
&
See par. 9.4 “HACCP alarms and display”
Tab. 3.b
(*) The default parameters, or any of the sets of parameters loaded inside MPXPRO,
only have eff ect on the parameters visible from the user terminal, based on the
list of parameters. The parameters that are not visible on the user terminal are not
aff ected by this procedure.