7. OPTIONAL CONFIGURATIONS
7.1 Other confi guration parameters
The other confi guration parameters that need to be set when
commissioning the controller concern :
• the measurement stability of analogue probes;
• the selection of the user terminal and/or remote display;
• the enabling of the keypad, remote control and buzzer (accessory);
• the standard display on the user terminal and the remote display;
• the display of messages / alarms on the remote display.
• the display in °C / °F and the decimal point;
• the locking of the buttons on the user terminal;
• the availability of the RTC (real time clock);
/2: Analogue probe measurement stability
Par. Description Def Min Max UoM
/2 Analogue probe measurement stability 4 1 15 -
Tab. 7.a
Defi nes the coeffi cient used to stabilise the temperature measurement.
Low values assigned to this parameter mean a prompt response of
the probe to variations in temperature; the reading however becomes
mostly sensitive to disturbance. High values slow down the response but
guarantee greater immunity to disturbance, that is, a more stable, more
precise and fi ltered reading.
/to: Select user terminal/remote display
Par. Description Def Min Max UoM
/to Confi gure user terminal/remote display
User terminal Remote display
0 Present Present
1 Optional Present
2 Present Optional
3 Optional Optional
303-
Tab. 7.b
This parameter used to select if the user terminal and/or the remote
display are optional, and are automatically recognised when fi tted. If the
required device is confi gured as optional, no alarm is generated on the
supervisor when absent.
H2: Disable keypad and remote control functions
Some functions relating to the use of the keypad can be disabled, for
example setting the parameters and the set point if the controller is
exposed to the public.
Par. Description Def Min Max UoM
H2 Disable keypad and remote control
functions
105-
Tab. 7.c
Below is a summary of the modes that are active for each setting:
Buttons Functions
H2
AUX
Prg/mute
UP/CC (conti-
nuous cycle)
DOWN/DEF
(defrost)
Set
Edit type F
parameters
Program
Set point
Settings
from remote
control
0 YES YES YES YES YES NO NO YES
1 YES YES YES YES YES YES YES YES
2 YES YES YES YES YES NO NO NO
3 YES YES YES YES YES YES YES NO
4 YES YES NO NO YES NO YES YES
5 YES YES NO NO YES NO NO YES
Tab. 7.b
When the set point and type F parameter setting functions are inhibited,
neither the set point nor the type F parameters can be changed, while
their values can still be displayed. The type C parameters, on the other
hand, being password protected, can also be set from the keypad,
following the procedure described previously. With the remote control
disabled, only the values of the parameters can be displayed, but they
cannot be modifi ed; in addition, the mute, defrost, continuous cycle, and
aux functions are disabled.
Note: If H2=2 or H2=3 is set on the remote control, this is
immediately disabled when pressing ESC. To re-enable the remote
control, set ‘H2’=0 or ‘H2’=1 from the keypad on the user terminal, on the
supervisor or in VPM.
/t1, /t2, /t: Display on user terminal and on remote display
Parameters /t1 and /t2 select the variable shown on the display during
normal operation. In the event of alarms, /t enables the display of alarms
on the remote display. For example, during defrost if /t=0 and d6 = 0, the
display does not show dEF alternating with the temperature set for /t2,
while when /t=1 the display shows dEF alternating with the temperature
set for /t2.
Par. Description Def Min Max UoM
/t1 Display on user terminal
0 = Terminal disabled
1 to 11 = Probe 1 to 11
12 = Control probe
13 = Virtual probe
14 = Set point
12014-
/t2 Display on remote display see /t1 12 0 14 -
/t Display signals / alarms on remote display
0 = disabled, 1 = enabled
001-
Tab. 7.d
/5, /6: Temperature unit of measure and display decimal point
Par. Description Def Min Max UoM
/5 Temperature unit of measure
0 =°C, 1=°F
001-
/6 Display decimal point
0 = enabled, 1 = disabled
001-
Tab. 7.e
Note: the pressure probe minimum and maximum limits vary
based on the selected unit of measure
H4: Disable buzzer
The buzzer on the user terminal can be disabled by setting parameter H4.
Par. Description Def Min Max UoM
H4 Terminal buzzer
0 = enabled; 1= disabled
001-
Tab. 7.f
H6: Terminal keypad lock confi guration
Parameter H6 is used to disable the functions relating to the individual
buttons on the keypad.
Par. Description Def Min Max UoM
H6 Terminal keypad lock confi guration 0 0 15 -
Tab. 7.g