8. TABLE OF PARAMETERS
Parameter levels: F = frequent, C=confi guration (password=22), A=advanced (password=33)
Par. Description Pag. Def Min Max UoM Type Icon
/Pro (=PROBES)
/2 Analogue probe measurement stability 55 4 1 15 - A
/4 Virtual probe composition
0 = Outlet probe Sm
100 = Intake probe Sr
34 0 0 100 % C
/5 Temperature unit of measure
0= °C/barg, 1= °F/psig
55 0 0 1 - A
/6 Display decimal point
0 = Enabled, 1 = Disabled
55 0 0 1 - A
rHS Virtual probe composition for glass temperature probe estimate
0 = Outlet probe Sm
100 = Intake probe Sr
43 20 0 100 % NV
/t Display signals / alarms on remote display
0 = Disabled, 1 = Enabled
55 0 0 1 - A
/t1 Display on user terminal
0 = User terminal disabled 8 = Serial probe 8
1 = Probe 1 9 = Serial probe 9
2 = Probe 2 10 = Serial probe 10
3 = Probe 3 11 = Serial probe 11
4 = Probe 4 12 = Control probe
5 = Probe 5 13 = Virtual probe
6 = Probe 6 14 = Set point
7 = Probe 7
55 12 0 14 - C
/t2 Display on remote display
0 = Remote display disabled 8 = Serial probe 8
1 = Probe 1 9 = Serial probe 9
2 = Probe 2 10 = Serial probe 10
3 = Probe 3 11 = Serial probe 11
4 = Probe 4 12 = Control probe
5 = Probe 5 13 = Virtual probe
6 = Probe 6 14 = Set point
7 = Probe 7
55 12 0 14 - A
/to Confi gure user terminal/remote display
User terminal Remote display
0 Present Present
1 Optional Present
2 Present Optional
3 Optional Optional
55 3 0 3 - A
/P1 Type of probe, group 1 (S1, S2, S3)
0 = NTC Standard Range –50T90°C
1 = PTC Standard Range –50T150 °C
2 = PT1000 Standard Range –50T150 °C
3 = NTC L243 Standard Range –50T90 °C
28 0 0 3 - A
/P2 Type of probe, group 2 (S4, S5)
0 = NTC Standard Range –50T90 °C
1 = PTC Standard Range –50T150 °C
2 = PT1000 Standard Range –50T150 °C
3 = NTC L243 Standard Range –50T90 °C
27 0 0 3 - A
/P3 Type of probe, group 3 (S6)
0 = NTC Standard Range –50T90 °C
1 = PTC Standard Range –50T150 °C
2 = PT1000 Standard Range –50T150 °C
3 = NTC L243 Standard Range –50T90 °C
4 = 0 to 5V ratiometric probe
27 0 0 4 - A
/P4 Type of probe, group 4 (S7)
0 = NTC Standard Range –50T90 °C
1 = PTC Standard Range –50150 °C
2 = PT1000 Standard Range –50T150 °C
3 = NTC L243 Standard Range –50T90 °C
4 = 0 to 5V ratiometric probe
5 = 0 to 10 V input
6 = 4 to 20 mA input
41 0 0 6 - A
/P5 Type of probe, group 5: serial probes (S8 to S11) 41 0 0 15 - A
/FA Assign outlet temperature probe (Sm)
0 = Function disabled 6 = Probe S6
1 = Probe S1 7 = Probe S7
2 = Probe S2 8 = Serial probe S8
3 = Probe S3 9 = Serial probe S9
4 = Probe S4 10 = Serial probe S10
5 = Probe S5 11 = Serial probe S11
30 1 0 11 - C
/Fb Assign defrost temperature probe (Sd) - See /FA 30 2 0 11 - C
/Fc Assign intake temperature probe (Sr) - See /FA 30 3 0 11 - C
/Fd Assign superheated gas temperature probe (tGS) - See /FA 27-41 0 0 11 - A
/FE Assign saturated evaporation pressure/temperature probe (PEu/tEu) - See /FA 27-41 0 0 11 - A
/FF Assign defrost temperature probe 2 (Sd2) - See /FA 41 0 0 11 - A