Par. Description Pag. Def Min Max UoM Type Icon
/FG Assign auxiliary temperature probe 1 (Saux1) - See /FA 41 0 0 11 - A
/FH Assign auxiliary temperature probe 2 (Saux2) - See /FA 41 0 0 11 - A
/FI Assign ambient temperature probe (SA) - See /FA 41 0 0 11 - A
/FL Assign ambient humidity probe (SU) - See /FA 41 0 0 11 - A
/FM Assign glass temperature probe (Svt) - See /FA 41 0 0 11 - A
/Fn Assign dewpoint value (SdP) to a serial probe
0 = Function disabled 3 = Serial probe S10
1 = Serial probe S8 4 = Serial probe S11
2 = Serial probe S9
41 0 0 4 - A
/c1 Probe 1 calibration 31 0 -20 20 (°C/°F) F
/c2 Probe 2 calibration 31 0 -20 20 (°C/°F) F
/c3 Probe 3 calibration 31 0 -20 20 (°C/°F) F
/c4 Probe 4 calibration 41 0 -20 20 (°C/°F) A
/c5 Probe 5 calibration 41 0 -20 20 (°C/°F) A
/c6 Probe 6 calibration 41 0 -20 20 (°C/°F/
barg/
RH%)
A
/c7 Probe 7 calibration 41 0 -20 20 (°C/°F/
barg/
RH%)
A
/U6 Maximum value of probe 6 27-41 9.3 /L6 160 if
/5=0
800 if
/5=1
barg/
RH%
A
/L6 Minimum value of probe 6 27-41 -1 -20 if /5=0
-90 if /5=1
/U6 barg/
RH%
A
/U7 Maximum value of probe 7 41 9.3 /L7 160 if
/5=0
800 if
/5=1
barg/
RH%
A
/L7 Minimum value of probe 7 41 -1.0 -20 if /5=0
-90 if /5=1
/U7 barg/
RH%
A
CtL (Control)
OFF ON/OFF control
0 = ON; 1 = OFF;
44 0 0 1 - A
St Set point 35 50 r1 r2 °C/°F F
St2 Intake probe set point with “Double thermostat 44 50 r1 r2 °C/°F A
rd Set point diff erential St 35 2 0.1 20 °C/°F F
rd2 Set point diff erential St2 with “Double thermostat”
0.0 = function disabled
44 0 0 20 °C/°F A
r1 Minimum set point 44 -50 -50 r2 °C/°F A
r2 Maximum set point 44 50 r1 50 °C/°F A
r3 End defrost signal by timeout
0 = disabled, 1 = enabled
48 0 0 1 - A
r4 Automatic night-time set point variation 35 0 -50 50 °C/°F C
r5 Maximum and minimum temperature monitoring probe
0 = monitoring disabled 6 = superheated gas probe (tGS)
1 = control probe (Sreg) 7 = saturated evaporation temp. probe (tEu)
2 = virtual probe (Sv) 8 = auxiliary defrost probe (Sd2)
3 = outlet probe (Sm) 9 = auxiliary probe (Saux)
4 = defrost probe(Sd) 10 = auxiliary probe 2 (Saux2)
5 = intake probe (Sr)
46 0 0 10 - A
rt Duration of the current maximum and minimum temperature monitoring session 46 - 0 999 hour A
rH Maximum temperature acquired in the session 46 - - - °C/°F A
rL Minimum temperature acquired in the session 46 - - - °C/°F A
r6 Probe for night-time control
0 = virtual probe Sv; 1 = intake probe Sr
35 0 0 1 - C
ro Control off set with probe error 45 0.0 0.0 20 °C/°F A
r7 Master solenoid valve confi guration
0 = local valve;1 = network valve (connected to Master)
36 0 0 1 - C
rSu Suction valve closure delay in normal regolation mode 47 0 0 999 sec C
CMP (compressor)
c0 Delay enable compressor and evaporator fans on power-up 47 0 0 240 min A
c1 Minimum time between successive starts 47 0 0 15 min A
c2 Minimum OFF time 47 0 0 15 min A
c3 Minimum ON time 47 0 0 15 min A
c4 ON time for duty setting operation (Toff = 15 minutes fi xed)
0 = compressor/valve always OFF; 100 = compressor/valve always ON
47 0 0 100 min A
cc Running time in continuous cycle 47 1 0 15 hour A
c6 Low temperature alarm bypass time after continuous cycle 47 60 0 240 min A