User manual
61
ENG
MPXPRO - + 0300055EN rel. 1.3 07/03/13
Par. Description Pag. Def Min Max UoM Type Icon
P12 LSA: alarm delay
0 = alarm disabled
55 600 0 999 s A
P13 LSA: alarm diff erential (°C)
0 = reset always automatic
55 10.0 0.0 60.0 °C/°F A
P14 Enable valve alarm at end travel (‘blo’)
1 = signal enabled
67 1 0 1 - A
P15 Support saturated temperature for pressure probe error 53 -15.0 -50.0 50.0 °C/°F A
PH Type of refrigerant
1 = R22 8 = R600 15 = R422D 22 = R407F
2 = R134a 9 = R600a 16 = R413A
3 = R404A 10 = R717 17 = R422A
4 = R407C 11 = R744 18 = R423A
5 = R410A 12 = R728 19 = R407A
6 = R507A 13 = R1270 20 = R427A
7 = R290 14 = R417A 21= R245Fa
28-51 3 1 22 - A
OSH Superheat off set for modulating thermostat
0 = function disabled
53 0.0 0.0 60.0 K A
Phr Enable fast update of the valve parameters to supervisor
0 = fast update disabled
52 0 0 1 - A
PM1 MOP: maximum saturated evaporation temperature threshold 54 50.0 -50.0 50.0 °C/°F A
PM2 MOP: integration time 54 10.0 0.0 240.0 s A
PM3 MOP: alarm delay
0 = function disabled
54 0 0 999 s A
PM4 MOP: delay activation of function when starting control 54 2 0 240 s A
PM5 MOP: enable close solenoid valve
0 = closing disabled; 1 = closing enabled
54 0 0 1 - A
PL1 LOP: minimum saturated evaporation temperature threshold 55 -50.0 -50.0 50.0 °C/°F A
PL2 LOP: integration time 55 0.0 0.0 240.0 s A
PL3 LOP: alarm delay
0 = function disabled
55 0 0 240 s A
SH Superheat 40-56 - - - K F
PPU Valve opening percentage 40-56 - - - % F
tGS Superheated gas temperature 40-56 - - - °C/°F F
tEu Saturated evaporation temperature 40-56 - - - °C/°F F
/cE Saturated evaporation temperature calibration 41 0.0 -20.0 20.0 °C/°F A
Po6 PWM expansion valve Ton + Toff period 56 6 1 20 s A
cP1 Initial valve position when control starts 52 30 0 100 % A
Pdd Initial valve position maintenance time after defrost 52 10 0 30 min A
PSb Valve standby position 52 0 0 400 step A
PF Valve opening steps (supervisor) 56 - 0 - step NV
PMP Enable manual expansion valve positioning
0 = disabled; 1 = enabled
56 0 0 1 - A
PMu Manual valve position 56 - 0 600 step A
Phc Enable high current valve driving 56 0 0 1 - A
PSM Smooth Lines - Enable function
52 0 0 1 -
A
PLt Smooth Lines - Off set to stop control below set point
52 2.0 0.0 10.0 °C/°F
A
PHS Smooth Lines - Maximum superheat off set
52 15.0 0.0 50.0 K
A
CnF (Confi guration)
In Type of unit
0 = Slave;1 = Master
28 0 0 1 - C
Sn Number of slaves in the local network
0 = no Slave
28 0 0 5 - C
H0 Serial or Master Slave network address 28 199 0 199 - C
H1 Confi gure function of output AUX1
0 = No function 7 = Auxiliary evaporator defrost
1 = Normally de-energized alarm 8 = Evaporator fans
2 = Normally energized alarm 9 = Anti-sweat heaters
3 = Auxiliary 10 = Suction valve
4 = Auxiliary serving MASTER on the Slaves 11 = Equalizing valve.
5 = Light 12 = Solenoid valve.
6 = Light serving the Master on the Slaves
33 8 0 12 - C
H2 Disable keypad and remote control functions
1 = keypad and remote control enabled
55 1 0 5 - A
H3 Remote control enabling code
0 = programming from remote control without code
33 0 0 255 - A
H4 Terminal buzzer (if present)
0 = enabled; 1= disabled
55 0 0 1 - A
H5 Confi gure function of output AUX2 see H1 33 2 0 12 - C
H6 Terminal keypad lock confi guration 55 0 0 15 - A
H7 Confi gure function of output AUX3 see H1 33 5 0 12 - C
H8 Output switched with time bands
0 = Light; 1 = AUX
33 0 0 1 - C
H9 Select function associated with the “aux” button on the user terminal
0 = Light; 1 = AUX.
33 0 0 1 - C
H10 Confi gure compressor digital output logic
0 = direct logic; 1 = reverse logic
44 0 0 1 - A