Par. Description Pag. Def Min Max UoM Type Icon
H11 Confi gure evaporator fan digital output logic
0 = direct logic; 1 = reverse logic
44 0 0 1 - A
H12 Light sensor threshold 42 25 10 100 lux A
H13 Confi gure function of output AUX4 see H1 33 12 0 12 - C
Hdn Number of default parameter sets available 18 0 0 6 - NV -
Htc Clock fi tted
0 = not fi tted
58 0 0 1 - A
rHu Manual anti-sweat heater activation percentage (of period ‘rHt’)
0 = function disabled
43 70 0 100 % A
rHt Manual anti-sweat heater activation period
0 = function disabled
43 5 0 180 min A
rHo O set for anti-sweat heater modulation 43 2.0 -20.0 20.0 °C/°F A
rHd Diff erential for anti-sweat heater modulation 43 0.0 0 20.0 °C/°F A
rHL Type of PWM output load for anti-sweat heater modulation
0 = resistive; 1 = inductive
43 0 0 1 - A
rHA Coeffi cient A for glass temperature probe estimate 43 2 -20 20 °C/°F NV -
rHb Coeffi cient B for glass temperature probe estimate 43 22 0 100 - NV -
HSt (Alarm log)
HS0 to 9 Alarm 0 to 9 (press Set) 68 - - - - A
--- Alarm 0 to 9 - Code 68 - - - - *
h__ Alarm 0 to 9 - Hours 68 0 0 23 hour *
n__ Alarm 0 to 9 – Minutes 68 0 0 59 min *
--- Alarm 0 to 9 - Duration 68 0 0 999 min *
HcP (HACCP alarms)
Ht0 HACCP alarms present 68 0 0 1 - NV -
HAn Number of type HA alarms 68 0 0 15 - A
HA to HA2 Type HA HACCP alarms activated (press Set) 68 - - - - A
y__ Alarm 1 to 3 - Year 68 0 0 99 year *
M__ Alarm 1 to 3 - Month 68 0 1 12 month *
d__ Alarm 1 to 3 – Day of the month 68 0 1 31 day *
h__ Alarm 1 to 3 – Hours 68 0 0 23 hour *
n__ Alarm 1 to 3 – Minutes 68 0 0 59 min *
--- Alarm 1 to 3 – Duration 68 0 0 240 min *
HFn Number of type HF alarms 68 0 0 15 - A
HF to HF2 Type HF HACCP alarms activated (press Set) 68 - - - - A
y__ Alarm 1 to 3 - Year 68 0 0 99 year *
M__ Alarm 1 to 3 - Month 68 0 1 12 month *
d__ Alarm 1 to 3 – Day of the month 68 0 1 31 day *
h__ Alarm 1 to 3 – Hours 68 0 0 23 hour *
n__ Alarm 1 to 3 – Minutes 68 0 0 59 min *
--- Alarm 1 to 3 – Duration 68 0 0 240 min *
Htd HACCP alarm delay
0 = monitoring disabled
68 0 0 240 min A
rtc (Real Time Clock)
td1 to 8 Defrost 1 to 8 (press Set) 36 - - - - C
d__ Defrost 1 to 8 – day
0 = event disabled 9 = Monday to Saturday
1 to 7 = Monday to Sunday 10 = Saturday to Sunday
8 = Monday to Friday 11 = every day
36 0 0 11 day *
h__ Defrost 1 to 8 – hours 36 0 0 23 hour *
n__ Defrost 1 to 8 – minutes 36 0 0 59 min *
P__ Defrost 1 to 8 – enable Power defrost
0 = normal; 1= Power defrost
36 0 0 1 - *
tS1 to 8 Start time band 1 to 8 day (press Set) 35 - - - - C
d Start time band 1 to 8 day: day 35 0 0 11 day *
h Start time band 1 to 8 day: hours 35 0 0 23 hour *
n Start time band 1 to 8 day: minutes 35 0 0 59 min *
tE1 to 8 End time band 1 to 8 day (press Set) 35 - - - - C
d End time band 1 to 8 day: day 35 0 0 11 day *
h End time band 1 to 8 day: hours 35 0 0 23 hour *
n End time band 1 to 8 day: minutes 35 0 0 59 min *
tc Date/time (Press Set) 22 - - - - C
y__ Date/time: year 22 0 0 99 year *
M__ Date/time: month 22 1 1 12 month *
d__ Date/time: day of the month 22 1 1 31 day *
u__ Date/time: day of the week 22 6 1 7 day *
h__ Date/time: hours 22 0 0 23 hour *
n__ Date/time: minutes 22 0 0 59 min *
Tab. 8.a