Specifications
SD Carel USA  
 11 
Wiring the CDP Proportional Controller 
The CDP controller is designed to accept 
various modulating input signals: 0-10 
Vdc, 0-20 Vdc, 2-10 Vdc, 0-20 mAdc and 
4-20 mAdc. The DIP switches located on 
the back of the controller must be set for 
the appropriate input signal. 
NOTE: the modulating signal must come 
from a controller or DDC system, not a 
sensor. The CDP controller follows the 
input signal being off at low signal and full 
on at full signal. 
Wiring the CDH Humidity Readout 
Proportional Controller 
The CDH controller is designed to accept 
an input signal from a humidity sensor 
(not controller). This input signal is then 
displayed on the controller as the relative 
humidity. Set point and differential are 
entered into the CDH controller making it 
stand-alone. 
Wiring the CDD Humidity Readout 
Proportional Controller/Dehumidify 
The CDD controller is designed to accept 
an input signal from a humidity sensor 
(not controller). This input signal is then 
displayed on the controller as the relative 
humidity. Set point and differential are 
entered into the CDD controller making it 
stand-alone. 
The connections 66-67 are only for 
connection to the Macrobase controller for 
humidification/dehumidification 
management of air handling units. Max: 
5ma, 30vdc. There is also a dehumidify 
contact that can be connected to a 
dehumidifier. The dehumidify contact is 
limited to 24 Vac/dc at 1 Amp. 
There is also a CDT controller that reads 
a temperature sensor input and controls the SD humidifier for use in a Turkish bath. It is wired the same was as the 
CDH controller, but with a temperature sensor instead. 