Specifications

Installation & Maintenance Manual__________
18
5.3 Control Wiring
The humidifier has proportional modulation with the ability to vary its capacity from 25 to 100% according to the
demands for humidity. The humidifier can be connected using RS485 to a remote panel Carel Humivisor (MT in the
following pictures) or to a remote supervisor or BAS system.
5.3.1 Control Wiring for C Type On/Off
The C Type control program is for On/Off operation in response
to an external closed contact as from a humidistat or DDC relay.
If the Hi-Limit and Airflow switches are not used, then place a
jumper across terminals 7Z and 8Z.
DO NOT apply voltage to any input on a C Type controller.
5.3.2 Control Wiring for P Type Proportional Modulating
The P Type control program is designed to accept various modulating input signals: 0-10 Vdc, 2-10 Vdc, 0-20
mAdc, and 4-20 mAdc from an external controller (R).
If the Hi-Limit and Airflow switches are not used, then place a jumper across terminals 7Z and 8Z.
NOTE: The modulating signal must come from a controller or DDC system, not a sensor. The P Type control
program follows the input signal directly, being off at low signal and full output at high signal.
1Z
2Z
3Z
4Z
5Z
6Z
7Z
8Z
9Z
10Z
11Z
12Z
13Z
14Z
External
Regulation
HI-LIMIT
HUMIDISTAT
AIRFLOW
SWITCH
Signal
Common
HI-LIMIT
HUMIDISTAT
AIRFLOW
SWITCH
H
1Z
2Z
3Z
4Z
5Z
6Z
7Z
8Z
9Z
10Z
11Z
12Z
13Z
14Z
R