Specifications
CAREL gaSteam 
19
5.3.4 Control Wiring for H Type Modulating With Humidity Display 
The H Type control program is designed to accept an input signal from a humidity sensor (HT), not a DDC 
signal. This humidity sensor input signal is then displayed on the controller as the relative humidity. The set 
point and differential are entered into the controller, making it stand-alone. Figure 5.5.1 is the wiring for the 
ASWH10000 wall mount sensor and the ASDH10000 duct mount sensor. Figure 5.5.1 also shows the control 
scheme. 
The H Type control program can also accept a second sensor (in this example shown as an ASDH10000 duct 
sensor), which acts as a high limit and will modulate the output down on approaching either the main set point 
or the high limit set point (see Figure 5.5.2). This is a very useful feature in VAV systems where the airflow can 
vary, and also in high precision applications where the on/off cycling of a high limit humidistat would be 
detrimental to precision. 
In place of the control humidity sensor, a temperature sensor could be used in applications where the humidifier 
will be used for a steam bath. 