5.3.5 Alarm Contact 
The controller also provides a SPDT relay contact for the remote indication of any alarm conditions. Connection 
to the alarm contact (max. voltage 250 Vac; max. capacity: 8A res. - 2A ind.) is made through the plug-in Z 
terminal block, as shown in Figure 5.6.1. 
5.3.6 Dehumidification Contact 
In the H Type control program, a SPST – N/O relay contact is available, which can be programmed to actuate 
an external dehumidifier. Connection to the dehumidifier contact (max. voltage 250 Vac; max. capacity: 8A res. 
- 2A inductive) is made through the plug-in Z terminal block, as shown in Figure 5.7.1. 
 Figure 5.6.1   Figure 5.7.1 
5.3.7 Remote Terminal/Supervisor System 
The controller of the humidifier can be connected to an RS485 serial line as shown in Figure 5.8.1, to ultimately 
connect to: 
•  A Carel control panel (see dedicated manual) to manage up to 4 humidifiers; 
•  A remote supervisor system. (Maximum network distance = 1 mile.) 
  Figure 5.8.1 