13. SPARE PARTS
Description: UG045 UG090
Drain pipe 1312342AXX 1312334AXX
Fill solenoid valve 1312087AXX 1312088AXX
Gasket kit UGKGUAR040 UGKGUAR090
Teflon-coated heat exchanger body 19C483A005 19C514A003
Anti-foam sensor 13C483A004 13C483A004
3 position level switch UGKSL00000 UGKSL00000
Stainless mesh filter 14C483A007 14C483A007
Flue gas temperature probe with connector 61C483A008 61C514A002
Cooling fan 1312546AXX 1312546AXX
Gas burner UGKBRUC045 UGKBRUC090
Electrical panel UGKBRUCO45 UGKBRUCO90
Drain pump 1312673AXX 1312673AXX
Drain pump pipe 13C479A001 13C479A001
NTC preheat probe NTC030WP000 NTC030WP000
Steam generator insulation 1614300AXX 1614301AXX
Flame detection electrode with cable 61C483A009 61C483A009
Ignition electrode 61C483A016 61C483A016
Ignition transformer ------------------
Gas valve 13C514A004
Gas valve control board UGCB00000M
gaSteam control board UGBE000000 UGBE000000
Panel transformer 09C483A006 09C483A006
Interface board URI0000000 URI0000000
Controller UGH0000000 UGH0000000
Relay 0100712AXX 01020001AXX
Socket 5931424AXX -----------------
Air-flow switch 1309556AXX -----------------
13.1 Fuses
Fuses F1 & F2 2A slow-blow
Fuse F3 6.3A slow-blow
14. Alarms
14.1 Table of Alarms
When an alarm condition occurs, the controller will indicate the alarm state and display the type of alarm.
In the case of a potentially dangerous alarm the controller will immediately shut down the humidifier.
For some alarm events (see chart) the controller will trip the alarm relay and display the fault simultaneously.
When the alarm condition clears, humidifier operation and the alarm relay may be automatically or manually
reset, depending on the type of alarm. The alarm message must be manually cleared (except for alarms “Ec”
and “CL”) by pressing the PRG/reset button. Some alarms may cause a total shutdown of the humidifier, in
which case the power supply must be disconnected. If the humidifier is not powered, the alarm relay will be
open, even if the alarm condition still exists. In case of the CL alarm (maintenance intervention requested), the
alarm can be reset only by setting the hour counter to zero, see “Resetting the hour counter to zero”.
The alarm “E1” may occur in two distinct situations:
1. Malfunction during the reading of the parameter memory (usually on start-up)
The default parameters are temporarily recalled without being stored in the parameter memory (the
parameters can be accessed and restored to their correct values).
The recall of the default parameters is recommended.
2. Malfunction during writing to the parameter memory (usually on pressing the PRG button)
Any modifications entered are cancelled; the parameters can be accessed, the values modified again and
the storing operation repeated.