8
3. Locating and Mounting 
Position the unit to keep the steam distribution lines as short as possible, except in the case of direct space 
humidification with a top-mounted blower. Plan to place the unit where enough space and floor support for the 
weight is available (see Dimensions and Weights). 
The clearance dimensions shown in this 
manual are for reference only and are 
the minimum required for maintenance of 
the humidifier. Local and National Codes 
should be consulted prior to final location 
and installation of the humidifier. CAREL 
cannot accept responsibility for 
installation code violations. 
The metallic surface of the humidifier will 
become hot during operation and may 
exceed temperatures of 120° F, therefore 
do not place the unit where this will 
cause personal discomfort or damage to 
other equipment. Position the humidifier 
in the space, observing the minimum 
space requirements shown below, for 
ease of operation and maintenance. 
ATTENTION: Ensure that the electrical 
compartment ventilator exhaust fan is 
free from obstruction. 
The unit must also be level and plumb, 
otherwise the float mechanisms that 
determine water levels in the humidifier 
will not function properly. Use the feet 
provided on the bottom of the humidifier 
to help adjust the level and plumb. 