humiSteam electrode steam humidifiers Installation Operation User Manual Read and save these instructions.
humiSteam CAREL 2
Installation, Operating & Maintenance Manual IMPORTANT BEFORE INSTALLING OR HANDLING THE HUMIDIFIER PLEASE CAREFULLY READ AND FOLLOW THE INSTRUCTIONS AND SAFE TY STANDARDS DESCRIBED IN THIS MANUAL AND ILLUS TRATED ON THE LABELS ATTACHED TO THE MACHINE. This humidifier produces non-pressurized steam by means of electrodes immersed in the water contained in the cylinder-boiler (hereafter called the cylinder).
humiSteam CAREL Table of Contents How The Humisteam Works.........................................................................................................................5 1 Installation ...............................................................................................................................................6 1.1 Positioning........................................................................................................................................6 1.2.
Installation, Operating & Maintenance Manual How The Humisteam Works HumiSteam is an electrode humidifier. It produces s team for humidification by passing electr ode current through the water i n the steam generator cylinder between metal electr odes . There are no heater el ements . Steam output is direc tly proportional to the c onducti vity of the water, and the amount of elec trode immers ed in the water.
humiSteam CAREL 1 Installation 1.1 Positioning The HumiSteam has been designed for wall mounting (although it can be placed on a stand) and, since it is an atmospheric steam humidifier, should be placed close to the point where the steam will be used, to minimize the steam hose length (and condensate). Certain clearances must be maintained around the unit: A Minimum 12 Dimension (inches) B 8 C 8 D 16 E F 28 <0.
Installation, Operating & Maintenance Manual 1.2 Mounting 1.2.1 Removing the front cover The front cover is secured by a capture screw located underneath the CAREL logo. Twist the CAREL logo to reveal the screw, and use a phillips head screwdriver to remove it. Then simply lift the front cover and pull out to remove it. Return it in reverse order. 1.2.2 Fastening to the wall Using the screws and anchors supplied, fasten the mounting bracket to the wall.
humiSteam CAREL 1.3 Plumbing 1.3.1 Water supply The HumiSteam must be supplied with water (not softened) having the following characteristics: Instant flow rate Connection Temperature limits Pressure limits Hardness limits Conductiv ity range Model UE 001-008 009-015 025-045 65 0.2 gpm 0.3 gpm 1 gpm 1.9 gpm 1/4" O.D. Compression 3/8" O.D.
Installation, Operating & Maintenance Manual See the following diagram for a drain line installation diagram Note: If utilizing the optional drain tempering dev ices, the drain line needs to be increased to a 2" minimum nominal size for the UE025 to UE065. WARNING: Do NO T use PVC piping unless the unit has the optional drain tempering valve installed.
humiSteam CAREL Water supply and drain connections are made according to the following diagram. Note: Drain line must be installed and plumbed to an open drain immediately after the unit. For proper operation of the unit, the open drain should be installed before the trap (if allow ed by local code). Physical location of the supply and drain connections are located as shown below. UE 010-015 UE 025-065 NOTE: Carel can provide a drain tempering system which limits the water drain to no more than 140°F.
Installation, Operating & Maintenance Manual 1.4 Steam distribution 1.4.1A Duct injection NOTE: If the ventilated steam distributor is to be used, then go to section 1.4.1B. Each unit has either 7/8” (22 mm), 1-1/4” (30 mm) diameter outlet or 1-5/8” (40 mm) diameter outlets. Some units have multiple outlets. The duct distributors and steam hose must be matched in size to the diameter of the steam outlets for the units: UNIT MODEL NUMBER UE001 No.
humiSteam CAREL Distributor pipes should be mounted per the diagrams shown below, with a minimum of 6” from the center of the distributor pipe to the top of the duct and 3” minimum to the bottom. To install the distributor pipes: 1. Cut a key shaped hole in the side of the duct to match the steam pipe and condensate return. 2. Apply silicone sealant to the mounting plate and insert the pipe through the hole and secure it with 4 sheet metal screws. 3.
Installation, Operating & Maintenance Manual 1.4.1B Room distribution blower units Refer to the manual supplied with the Room Distribution Units for specifics on the blower units themselves. Clearances required are shown below.
humiSteam CAREL 1.4.2 Steam Hoses NINETY PERCENT (90%) OF ALL OPERATION PROBLEMS ARE CREATED BY IMPROPER STEAM PIPING FROM THE HUMIDIFIER UNIT TO THE DUCT DIS TRIBUTOR PIPES. To avoid these problems, remember one simple fact when running the steam hose: steam naturally flows up hill, and condensate naturally flows down hill.
Installation, Operating & Maintenance Manual 1.5 Power wiring Single Phase Terminals Three Phase Terminals Check that the power supply voltage to be connected matches the value indicated on the rating plate inside the electrical panel. Insert the power and ground connection cables into the electrical panel compartment using the strain reliefs supplied, and connect to the terminals. An external fused disconnect must be installed.
humiSteam CAREL Voltage Voltage Nominal Code Phase Current (Amps) Model U 208 - 1~N 5.4 UE001 D 230 - 1~N 4.9 U 208 - 1~N 10.8 D 230 - 1~N 9.8 UE003 W 208 - 3~ 6.2 K 230 - 3~ 5.6 M 460 - 3~ 2.8 U 208 - 1~N 18 D 230 - 1~N 16.3 W 208 - 3~ 10.4 UE005 K 230 - 3~ 9.4 M 460 - 3~ 4.7 N 575 - 3~ 3.8 W 208 - 3~ 16.7 K 230 - 3~ 15.1 UE008 M 460 - 3~ 7.5 N 575 - 3~ 6 U 208 - 1~N 31.4 UE009 D 230 - 1~N 29.3 W 208 - 3~ 20.8 K 230 - 3~ 18.8 UE010 M 460 - 3~ 9.4 N 575 - 3~ 7.5 W 208 - 3~ 31.2 K 230 - 3~ 28.
Installation, Operating & Maintenance Manual 1.6 Connect Control Wiring A typical humidifier control system includes a wall or return duct sensor or controller, a high limit duct humidistat and an air-proving switch. Placement of these devices is critical to proper operation of the overall system. 1.6.1 Controls Placement (See following diagram) The return air RH sensor must always be located BEFORE any outside air intake, in order to insure accurate sensing of the air from the space.
humiSteam CAREL Remote Supervisor / Serial Communications: This is a standard RS485 serial connection. It is recommended to keep wiring under 3,200 feet. Request Carel’s communications documentation for additional information on this option. Control wiring is made directly to the control board terminals: 1. terminal block G (dehumidification contact); 2. terminal block H (alarm contact); 3. terminal block K (on/off, manual drain switch); 4. terminal block I (control signals); 5.
Installation, Operating & Maintenance Manual For Modulating Operation w ith External Controller: Connect any external controller (0-1 Vdc, 0-10 Vdc Parameter A0 must be set to 1. Parameter A2 must be set per the OUT signal from the regulator: • voltage: 0 to 1 Vdc; 0 to 10 Vdc; 2 to 10 Vdc; • current: 0 to 20 mA; 4 to 20 mA. NOTE: Safeties are high-limit humidistat, air flow switch, and/or external enable. DO NOT apply any v oltage to 7I & 8I.
humiSteam CAREL ASWH / ASDH – ASDH / ASDC Wall – Duct Temperature/Humidity Sensors Model Description Temperature: NTC thermistor, 10 Kohm at 25°C (77°F) (ASWC/ASDC onl y) Accurac y: +- 0.
Installation, Operating & Maintenance Manual HC-101 and HC-201 Wall and Duct Humidistats Mounting the HC-101 room humidistat: Mount the HC-101 humidistat to an inside wall or post in the area to be humidified. Position it so that no drafts from registers or outlets are blowing on it. Be sure that it is not placed over a device that could generate heat or vapor ie: stove, machinery, cleaning vat. The unit has three wire leads, Orange, Brown and Red. Use the Orange and Brown leads for control operation.
humiSteam CAREL PC-301 Air Proving Switch Mounting the PC-301 air flow switch: Mount the airflow switch in the supply or return duct using the screws supplied. Mount the device so that the diaphragm is in a vertical position as shown at right. If the airflow switch is to be mounted on the return duct (vacuum), then mount it in a vertical position by the small plate.
Installation, Operating & Maintenance Manual 2 Start-Up IMPORTANT WARNINGS: 1. Before starting, check that the humidifier is in perfect condition, that there are no water leaks and that the electrical parts are dry; 2.
humiSteam CAREL 2.2 The HumiControl Controller 1: PRG - Access to most frequently used parameters. Also resets alarm relay. 2: SEL - Displays unit of measure. Press for 2 seconds to access set point. Press with PRG for 5 seconds to enter parameters. 3: - Displays control sensor value. In programming mode increases value or moves to previous parameter. 4: - Displays high limit sensor value. In programming mode decreases value or moves to following parameter.
Installation, Operating & Maintenance Manual 3 Operation 3.1 Display Information Pressing the SEL button displays the unit of measure currently in use for the main display Holding the button displays the value of the control sensor preceded by the unit of measure. Holding the button displays the value of the high-limit sensor preceded by the unit of measure. 3.2 Changing The Set Point Press the SEL button for 2 seconds until “St” appears.
humiSteam CAREL Code Range Default Unit 100 %RH Hi-limit set point 2.0 to 19.9 5 0 to 100 100 %RH %RH Hi-limit differential Hi-limit alarm set point P7 (1) St to 100 P8 P9 Code Range d1 (2) 0.0 to 199 d2 0.0 to 199 d3 0.0 to 199 0.0 to 19999 0 to 1555 0.0 to 199 0.
Installation, Operating & Maintenance Manual A6 0 to 4 0 A7 0 to A8 0 A8 A7 to 100 100 A9 -10.0 to 10.
humiSteam CAREL Parameters for setting the serial connections and remote control: Code Range C0 1 to 6 Unit 1 C1 0 to 4 4 C2 C3 C4 0 to 99 0 to 199 0 to 3 0 1 3 C5 0 to 11 0 C6 0 to 199 0 C7 0 to 3 0 Description 1= room sensor measurement 2= outlet sensor measurement 3= steam output 4= hour counter 5= conductivity 6= current Value normally displayed Enable keypad and remote control - keypad: remote control: 0= read of all param., (modify C1 only) read and modify param.
Installation, Operating & Maintenance Manual STANDARD CONFIGURAT ION SETTINGS HumiSteam Parameters H Controller Parameter DDC 0-10 vdc DDC 4-20ma ON / OFF A0 A1 A2 A3 A4 A5 A6 A7 A8 A9 b1 b2 b3 b4 b5 b6 b7 b8 b9 bb bE bF C0 C1 C2 C3 C4 C5 C6 C7 d1 d2 d3 d4 d5 d9 P0 P1 P2 P3 P4 P5 P6 P7 P8 P9 ST 1 1 1 N/A N/A N/A N/A N/A N/A N/A 2 0 0.0 0 1.5 2.0 75 100 100 0 N/A 3 1 4 0 1 3 0 0 0 ∗ ∗ ∗ ∗ ∗ ∗ 100 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 1 1 4 N/A N/A N/A N/A N/A N/A N/A 2 0 0.0 0 1.5 2.
humiSteam CAREL 3.6 Seasonal Shut Down During seasonal shut-down or alternatively shut-down for maintenance of the electrical parts and/or the plumbing, the humidifier should be placed out-of-service. NOTE: the w ater cylinder should be emptied before shutting dow n the humidifier, to prevent corrosion of the electrodes.
Installation, Operating & Maintenance Manual 3.
humiSteam CAREL Controller Humivisor Causes Solution H EF E114 EA E115 Ed E116 Ec E131 E - EE = 1. Check that the fill pipe from the main to the humidifier and the internal pipe are not blocked or bent and that there is sufficient pressure (0.1-0.8 mpa, 1-8 bar) 2. Check the operation of the fill valve Lack of water 3. Check that the steam outlet is not working against excessive back-pressure, preventing the flow of water into the cylinder by gravity 4.
Installation, Operating & Maintenance Manual Controller Humivisor H E0 E101 EI E112 E2 E130 E3 E120 E4 CP CL E123 E132 E133 EU E134 PC - Cy Nn Causes Solution Action Reset Alarm Reset display relay relay H 1. Reset the default parameters Reprog. Internal memory (see Chap. 7.5) Shut- Reprog. Active By 2. If the problem persists, contact error down By Carel Carel the CARE service center 1.
humiSteam CAREL Controller Humivisor Causes Solution H Dr Idr Dr AF Action H - - - - Complete draining of the cylinder activated Complete draining for extended inactivity Complete periodical draining active Reset Alarm Reset display relay relay You have activated the manual drain sequence. Sequence ends on its own. - - - - The unit is emptying the cylinder after an extended period of non-use. Sequence ends on its own.
Installation, Operating & Maintenance Manual 3.10 Trouble-Shooting problem causes solutions 1. no electrical power 2. on/off switch of the humidifier in position 0 (open) the humidifier does not turn on 3. control connectors improperly connected 4. blown fuses 5. transformer failure 1. check the safety devices upstream from the humidifier and the presence of power 2. close the switch on the panel: position I 3. check that the connectors are properly inserted in the terminal block 4.
humiSteam CAREL problem Water in the cylinder turns black causes 1. minerals in the cylinder have overconcentrated and are deteriorating the electrodes. Heavy arcing occurs within hours of startup 1. The feed water contains large amounts of Iron, Copper or other conductive contaminants. Humidifier continuously fills and drains without producing steam 1. Mineral has bridged between the electrodes. 2. There is back pressure from the steam hoses or duct. 3.
Installation, Operating & Maintenance Manual 4 Maintenance 4.1 Periodic checks • • • • • After one hour of operation: For both disposable and cleanable cylinders, check that there are no significant water leaks. Ev ery fifteen days or no more than 300 operating hours: For both disposable and openable cylinders check operation, that there are no significant water leaks and the general condition of the cylinder. Check that during operation there is no arcing between the electrodes.
humiSteam CAREL Wiring of cylinders for UE025, UE035, UE045, UE065 units and v oltages Connection of single or three phase UE 001 to 015 models Note: Photo does not r epres ent all cylinder possibilities Connection of three phase UE 025 to 065 models Note: Photo does not represent all cylinder possibilities Model 025 035 045 065 Conductiv ity 125/350 350/1250 125/350 350/1250 125/350 350/1250 125/350 350/1250 Power Supply (Vac) 230 460 A B B B A B A B A B A B / B / B 208 A B A A A A / / 38 575 B B
Installation, Operating & Maintenance Manual UE001-UE015 4.2.2 Maintenance of the other plumbing components IMPORTANT WARNINGS: • When cleaning the plastic components do not use detergents or solvents; ® ® • Scale can removed using a solution of Lime-A-Way , CLR , or 5% phosphoric acid, then rinse with water. • External power must always be disconnected when performing any maintenance on the humidifier.
humiSteam CAREL 4.3 Replacement Parts 4.3.
Installation, Operating & Maintenance Manual Standard Spare Parts Model UE003 UE005 UE008 UE010 UE015 UE025 Control Module Ver. H-T UEH0000000U00 Control Board Ver. C-P ** UEP0000000U00 UE035 UE045 UE065 Control Board Ver.
humiSteam CAREL electrod e kit 460/3 VAC Low con ductivity KITBLCT2C0 KITBLCT2C0 KITBLCT3C0 KITBLCT3C0 KITBLCT4D0 KITBLCT4C0 KITBLCT4C0 KITBLCT5C0 electrod e kit 575/3 VAC Low con ductivity KITBLCT2C0 KITBLCT2C0 KITBLCT3C0 KITBLCT3C0 KITBLCT4D0 KITBLCT4D0 KITBLCT4D0 KITBLCT5D0 electrod e gasket kit KITBLC2FG0 KITBLC2FG0 KITBLC3FG0 KITBLC3FG0 KITBLC4FG0 KITBLC4FG0 KITBLC4FG0 KITBLC5FG0 KITBLC5FG0 Low Co nductiv ity cylind ers for water cond itions b etwee n 125- 350 µS/cm Standard
Installation, Operating & Maintenance Manual 5 Wiring Diagrams UE001, UE003, UE005, UE009 Single Phase 43
humiSteam CAREL UE003, UE005, UE008, UE010, UE015 Three Phase 44
Installation, Operating & Maintenance Manual UE025, UE035, UE045, UE065 Three Phase 45
humiSteam CAREL 6 Technical Specifications VAC/ Phase UNIT MODEL NUMBER: Capacity, Amperage, Kilowa tts Factor UE 001 UE 003 UE 005 Lbs/hr 3.3 6.6 11.0 19.1 kg/h 1.5 3 5 8.7 Amps 5.4 10.8 18.0 31.3 KW 1.12 2.25 3.75 6.52 Lbs/hr 3.3 6.6 11.0 19.8 kg/h 1.5 3 5 9 Amps 4.9 9.8 16.3 29.3 KW 1.12 2.25 3.75 6.75 Lbs/hr 6.6 11.0 kg/h 3 5 Amps 6.2 KW 2.
Installation, Operating & Maintenance Manual 6.1 Model Numbers UE 025 H D 000 U 1 0 UE = Electrode Capacity H Control Power supply Version number USA Cylinder Type Optional Equipment 001 = 3.
humiSteam CAREL CAREL USA, LLC 385 S. Oak Street Manheim, PA 17545 Form: +030221907, Rev . 0.