1.4.1B Room distribution blower units
Refer to the manual supplied with the Room Distribution Units for specifics on the blower units themselves.
Clearances required are shown below.
Model
UE001
UE003
UE005
UE008
UE009 UE010 UE015
UE025
UE035
UE045
UE065
Room Blower
Unit Model
VSDU0A VRDXL
Rated Power
Watts
30 35
Air Volume
CFM
100 380
Noise Level
dBA
50 40
Operati ng Temp/Humidity
(°F / %RH)
14 to 104°F
/ 10 to 60%
14 to 140°F
/ 10 to 80%
Cold rooms can be humidified using a Room Distribution Unit, making sure that this operates within its
operating limits. The room must have operating temperatures of between -10°C and +20°C, with a percentage
of relative humidity of no greater than 80% RH. If these limits are not possible, the steam can be distributed in
the cold room using a distributor pipe in duct work. In any case, the steam must not come into direct contact
with air discharge from the refrigeration unit in the cold room, to avoid possible condensation.
VSDU0A
A B C D E F H
20 72 72 24 20 72 24
VRDXL
Minimum
dimension
(inches)
36 120
72 48 36 120
48