User manual

CAREL
humiSteam
16
Model
Voltage
Code
Voltage
Phase
Nominal
Current
(Amps)
Power
(kW)
Output
(kg/hr)
Output
(lbs/hr)
Turns
Through
TAM
TA Rate
U 208 - 1~N 5.4 1 20
UE001
D 230 - 1~N 4.9
1.12 1.5 3.3
2 20
U 208 - 1~N 10.8 2 60
D 230 - 1~N 9.8 1 20
W 208 - 3~
6.2 1 20
K 230 - 3~
5.6 1 20
UE003
M 460 - 3~
2.8
2.25 3 6.6
2 20
U 208 - 1~N 18 1 40
D 230 - 1~N 16.3 1 40
W 208 - 3~
10.4 1 20
K 230 - 3~
9.4 1 20
M 460 - 3~
4.7 2 20
UE005
N 575 - 3~
3.8
3.75 5 11
2 20
W 208 - 3~
16.7 1 40
K 230 - 3~
15.1 2 60
M 460 - 3~
7.5 1 20
UE008
N 575 - 3~
6
6 8 17.6
1 20
U 208 - 1~N 31.4 1 60
UE009
D 230 - 1~N 29.3
6.52 9 20
1 60
W 208 - 3~
20.8 1 40
K 230 - 3~
18.8 1 40
M 460 - 3~
9.4 1 20
UE010
N 575 - 3~
7.5
7.5 10 22
1 20
W 208 - 3~
31.2 1 60
K 230 - 3~
28.2 1 60
M 460 - 3~
14.1 1 20
UE015
N 575 - 3~
11.3
11.25 15 33
1 20
W 208 - 3~
52 1 300
K 230 - 3~
47.1 1 300
M 460 - 3~
23.5 1 300
UE025
N 575 - 3~
18.8
18.75 25 55
1 300
W 208 - 3~
72.9 1 500
K 230 - 3~
65.9 1 500
M 460 - 3~
32.9 1 500
UE035
N 575 - 3~
26.4
26.25 35 77
1 300
W 208 - 3~
93.68 1 500
K 230 - 3~
84.72 1 500
M 460 - 3~
42.4 1 500
UE045
N 575 - 3~
33.9
33.75 45 99
1 500
M 460 - 3~
61.19 1 300
UE065
N 575 - 3~
48.95
48.75 65 143
1 300
NOTE: Tolerance allowed on main voltage = -15%, +10%