ASWH / ASDH – ASDH / ASDC Wall – Duct Temperature/Humidity Sensors
Model Description
Humidity (0-1 VDC or 4-20 mADC)
ASWH100000
Wall Humidit y sensor (replaces SHWOOP)
ASDH100000 Duct Humidity sensor (repl aces SSDOMH00/1)
Temperature & Humidity (NTC temp, 0- 1 VDC or 4-20 mADC humidity)
ASWC111000
Wall Temp/hum sens or (replaces SWNTCTH0/1 & STHONTC0/1)
ASWC110000
Wall Temp/hum sens or (replaces STHOAP)
Temperature & Humidity (0-1 VDC or 4-20 Mad c temp & humidity)
ASDC111000 Duct temp/hum sens or (replac es SDNTCTH0/1)
ASDC110000 Duct temp/hum sens or (replac es SSDOMHT0/1)
Temperature: NTC thermist or, 10 Kohm at 25°C (77°F)
(ASWC/ASDC onl y)
Accurac y: +- 0.25°C from 0 to 50°C (32 to 122°F)
Humidity: Thi n film capacitor
Linear 0-1 Vdc or 4-20 mAdc from 10 to 90%RH
Accurac y: +- 3%RH fr om 20 to 90%RH
calibrated at 55%RH and 25°C (77°F)
+- 5%RH above 90%RH and below 20%RH
Response time: 60 sec onds
Power: 12 t o 24 Vac/dc or +12 to –12 Vdc
Housing: Wall: ABS with glassfiber fill
Certifications: Calibrated to NIST trac eable
humidity/temperature s tandar d, CE Approved