User manual

Installation, Operating & Maintenance Manual 
  3 
IMPORTANT 
BEFORE INSTALLING OR HANDLING  THE HUMIDIFIER PLEASE CAREFULLY READ AND FOLLOW THE 
INSTRUCTIONS AND SAFETY STANDARDS DESCRIBED IN THIS MANUAL AND ILLUSTRATED ON THE 
LABELS ATTACHED  TO THE MACHINE.  
This humidifier produces non-pressurized steam by means of electrodes immersed in the water contained in 
the cylinder-boiler (hereafter called the cylinder). The electrodes pass current through the water, which also 
provides resistance, heating the water into steam, which is used to humidify environments or industrial 
processe s, using special distributors.  
The quality of the water used affects the process of evaporation, so the humidifier may be supplied with 
untreated water, as long as this is drinkable and not softened or demineralized; the evaporated water is 
automatically replaced using a fill valve. This humidifier has been designed exclusively to directly humidify 
rooms or ducts, using a distribution system. The installation, use and maintenance operations must be carried 
out according to the instructions contained in this manual and on the labels applied internally and externally.  
The conditions of the env ironment and the power supply v oltage must comply w ith the specified 
values. 
All other uses and modifications made to the humidifier that are not authorized by the manufacturer are 
considered incorrect. 
Liability for inj ury or damage caused by the incorrect use of the humidifier lies exclusively with the 
user.  
Please note that the humidifier contains pow ered electrical devices and hot surfaces. 
All service and/or maintenance operations must be performed by specialist and qualified personnel 
w ho are aware of the necessary precautions and are capable of performing the operations correctly.  
Disconnect the humidifier from the main pow er supply before accessing any internal parts. 
The humidifier must be installed in accordance w ith the local standards in force. 
The local safety standards in force must be applied in all cases. 
The humidifier is made up of metallic and plastic parts. All parts must be disposed of according to the 
local standards on waste disposal.  
Certification: the quality and safety of CAREL products are assured by CAREL's ISO 9001 certified design 
and production system, as well as listings from UL, cUL, CE, TUV, ETL and others. 
WARNING: Your humidifier requires water to operate.  Do NOT mount it above materials or machinery that 
could be damaged if a leak occurs.  Carel assumes no responsibility for consequential or inconsequential 
damage as a result of any leaks. 
Copyright © 2005 by Carel USA, LLC. All rights reserved. 