User manual

CAREL
humiSteam
34
Controller Action
H
Humivisor Causes Solution
H
Reset
display
Alarm
relay
Reset
relay
Dr
-
Complete
draining of the
cylinder
activated
You have activated the manual
drain sequence. Sequence ends on
its own.
- - - -
Idr
-
Complete
draining for
extended
inactivity
The unit is emptying the cylinder
after an extended period of non-
use.
Sequence ends on its own.
- - - -
Dr
-
Complete
periodical
draining active
The unit has activated the periodic
drain to flush excessive minerals.
Sequence ends on its own.
- - - -
AF
-
Anti-foam
algorithm active
The unit is working to eliminate
foaming.
- - - -