Case 2: several controllers connected in network powered by the different
transformers (G0 not connected to earth). Typical application of several controllers
that are part of different electric control boards.
!
Attention:
If one transformer is used to supply both the μC
2
SE and the accessories, all
the G0 terminals on the various controllers or the various boards must be
connected to the same terminal on the secondary, and all the G terminals to
the other terminal on the secondary, so as to avoid damaging the controller;
for use in residential environments, use shielded cable (two wires + shield
earthed at both ends, AWG 20-22) for the tLAN connections (EN 55014-1);
avoid short-circuits between V+ and GND so as not to damage the controller.
perform all the maintenance and installation operations when the unit is not
connected to the power supply;
separate the power cables (relay outputs) from the cables corresponding to
the probes, digital inputs and serial line;
use a transformer dedicated exclusively to the electronic controllers for the
power supply.
2.8.3
Protection against electric shock and
maintenance warnings
The system made up of the control board (MCH200005*) and the other optional
boards (MCH2000060, MCH2004850, MCHRTF****, CONVONOFF0, CONV0/10A0,
EVD000040*) constitutes a control device to be integrated into class I or class II
appliances. The class of protection against electric shock depends on how the
control device is integrated into the unit built by the manufacturer.
The protection against short circuits due to faulty wiring must be guaranteed by the
manufacturer of the appliance that the controller will be fitted on.
2.9
Programming key (copy of the set-up)
The PSOPZKEY00 and PSOPZKEYA0 programming keys for CAREL controllers allow
to copy the complete set of µC
2
SE parameters. The keys must be connected to the
connector (AMP 4 pin) envisioned in the controllers and can operate with
instruments that are live or not, according to that indicated in the user notes of the
specific controller. There are two main functions envisioned and they are selected
via two dip switches (situated under the battery lid). These are:
loading the parameters of a controller into the key (UPLOAD);
copying the key onto one or more controllers (DOWNLOAD.
!
Parameters can only be copied via controllers with the same code. The data
loading operation into the key (UPLOAD) is always allowed. To facilitate
identification of the key to be used, CAREL has enclosed a label on which the
programming loaded can be described or the machine to which it refers.
The key can only be used on µC
2
SE controllers that have the same Firmware
version.
2.9.1
UPLOAD - copy parameters from
controller to key
Procedure:
open the rear door of the key and position the two dip-switches at OFF. Close
the door;
connect the key to the controller terminal;
press the key button and hold, checking the signalling sequence of the LED:
from red, it turns green after a few seconds;
if the signalling sequence is that indicated above, the copying operation has
been successful (green LED on); the button can be released and the key
disconnected from the instrument. In the event of different signals: if the
green LED does not switch on or if flashing, there is a problem. See the
following table for the meanings of the signals.
2.9.2
DOWNLOAD - copy the parameters from
the key to controller
Procedure:
open the rear door of the key and position dip-switch n. 1 at OFF and dip-
switch n. 2 at ON. Close the door;
connect the key to the controller;
press the key button and hold, checking the signalling sequence of the LED:
from red, it turns green after a few seconds;
if the signalling sequence is that indicated above, the copying operation has
been successful (green LED on); the button can be released. After a few
seconds the LED switches off and the key can be disconnected from the
instrument;
in the event of different signals: if the green LED does not switch on or if
flashing, there is a problem. See the relative table for the meanings of the
signals.
The operation is completed in 10 seconds. If the completed signal with green LED
on is not given within this time period, it is good practice to attempt the operation
again, releasing and pressing the button again. In the event of flashing, see the
relative table for the meaning of the signal.
signal
LED
error meaning and solution
red LED
flashing
Batteries flat
start copy
The batteries are flat, the copy cannot
be made. Replace the batteries (only
for PSOPZKEY00).
Green LED
flashing
Batteries flat
copy end (only for
PSOPZKEY00)
The copy operation has been
performed correctly but at the
end of the operation the battery
voltage is low.
Flashing
simultaneously
red/green LED
(signal
orange)
Instrument not
compatible
The parameters set-up cannot be
copied because the controller model
connected is not compatible. This
error only for DOWNLOAD function,
check the controller code and copy
only onto compatible codes.
Red and green
LEDs on
Copy error Error in the data copied. Repeat the
operation, if the problem persists,
check the batteries and key
connections.
Red LED on
stable
Data transfer error The copy operations has not
terminated due to serious
data transfer or copy errors. Repeat
the operation, if the problem persists,
check the batteries and key
connections.
LEDs off Batteries
disconnected
Check batteries (for PSOPZKEY00)
Power supply unit not
connected
Check power supply unit (for
PSOPZKEYA0)
Fig.1 Fig.2
12