User manual
µC
2
SE process chiller +030220416 - rel. 2.2 - 25.01.2013
The low load differential is r29. This parameter represents the new differential
considered by the controller during the low load condition. Specifically r02 is
replaced by r29.
Par. Description
Def
Min
Max
U.M.
r27 Accumulation vessel suppression (low load)
0=Disabled
1=Enabled
2=Do not select
3=Do not select
0 0 3 -
r28 Min. compressor running time for low load 60 0 999 s
r29 Low load differential 3 1 50 °C/°F
evaporator
t
a
n
k
u
s
e
r
s
20