User manual


µC
2
SE process chiller +030220416 - rel. 2.2 - 25.01.2013

Par.
Description
Level
min
max
U.M.
Def.
Visibility
SVP CAREL
ModBus®
R/W
Variable type
H09 Lock keypad
0 = keypad disabled
1 = keypad enabled
U01-
1 -
16 16 R/W D
H10 RS485 serial address U 1 200 -
1 -
58 265
R
I
H11 Outputs setting (table)
F
012-
0 -
59 266 R/W I
H11
0 1 2 3 4 5 6
NO1 compressor 1 compressor 1 compressor 1 compressor 1 compressor 1 compressor 1 compressor 1
NO2 heater 1 heater 1 heater 1 - - heater 1 heater step 1
NO3 evaporator pump evaporator pump
evaporator pump
evaporator pump evaporator pump evaporator pump -
NO4 - compressor 2 (or
compressor 1
partialisation)
compressor 2
(or compressor 1
partialisation)
compressor 2
(or comp.1
partialisation)
compressor 2
(or comp.1
partialisation)
condenser fan -
NO5 alarm alarm - alarm alarm alarm alarm
7 8 9 10 11 12
NO1 compressor 1 compressor 1 compressor 1 compressor 1 compressor 1 compressor 1
NO2 heater step 1 heater step 1 compressor 2 compressor 2 compressor 2 P25
NO3 - - - - - P26
NO4 heater step 2 condense
r
fan - heating step 1 heating step 1 P27
NO5 alarm alarm alarm alarm alarm P28
30